Choice of flux density in transformer design
Short answer
Flux density is chosen high to reduce core size, but limited by iron loss, magnetizing current, noise and steel grade. Distribution transformers use 1.35–1.55 T (CRGO) or 1.1–1.35 T (hot‑rolled) for high all‑day efficiency; power transformers can use up to 1.75 T with CRGO.
How is the flux density in the design of transformer chosen?
The maximum flux density in the core is chosen as high as possible to reduce the size and cost of the core, but it is limited by iron loss, magnetising current, noise and the type of steel.
Factors deciding
- Core loss and efficiency: hysteresis loss ∝ and eddy loss ∝ . Higher means more iron loss and lower all-day efficiency.
- Magnetising current: near the knee of the B–H curve the mmf rises sharply, so and its harmonics increase.
- Type of transformer: distribution transformers are energised 24 h, so a lower is used to keep iron loss low. Power transformers can use higher values.
- Grade of steel: cold-rolled grain-oriented (CRGO) steel has low loss and high permeability along the grain, so it allows higher than hot-rolled steel.
- Over-voltage and frequency: margin is kept so the core does not saturate at overvoltage or reduced frequency.
- Noise: magnetostriction hum increases with .
Usual values
| Steel / transformer | (Wb/m²) |
|---|---|
| Hot-rolled silicon steel, distribution | 1.1–1.35 |
| Hot-rolled, power transformer | 1.25–1.45 |
| CRGO, distribution | 1.35–1.55 |
| CRGO, power transformer | 1.55–1.75 |
So is a compromise between a small core (high ) and low iron loss, low no-load current and low noise (low ).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- True/False: magnetic loading and teeth flux density · Electric Machine Design, chapter 5
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Numerical: received power, E-field, flux density, voltage · Wireless Communication, chapter 3 · asked 2×
- Flux and flux density in iron ring with 2 mm gap · Electrical Machines I, chapter 1 · asked 2×
- Cyclotron deuterons, flux density and energy · Engineering Physics, chapter 8
- Short note: Power flux density · Propagation and Antenna, chapter 2