Choice of flux density in transformer design

Short answer

Flux density is chosen high to reduce core size, but limited by iron loss, magnetizing current, noise and steel grade. Distribution transformers use 1.35–1.55 T (CRGO) or 1.1–1.35 T (hot‑rolled) for high all‑day efficiency; power transformers can use up to 1.75 T with CRGO.

How is the flux density in the design of transformer chosen?

The maximum flux density BmB_m in the core is chosen as high as possible to reduce the size and cost of the core, but it is limited by iron loss, magnetising current, noise and the type of steel.

Factors deciding BmB_m

  1. Core loss and efficiency: hysteresis loss ∝ Bm1.6B_m^{1.6} and eddy loss ∝ Bm2B_m^2. Higher BmB_m means more iron loss and lower all-day efficiency.
  2. Magnetising current: near the knee of the B–H curve the mmf rises sharply, so I0I_0 and its harmonics increase.
  3. Type of transformer: distribution transformers are energised 24 h, so a lower BmB_m is used to keep iron loss low. Power transformers can use higher values.
  4. Grade of steel: cold-rolled grain-oriented (CRGO) steel has low loss and high permeability along the grain, so it allows higher BmB_m than hot-rolled steel.
  5. Over-voltage and frequency: margin is kept so the core does not saturate at overvoltage or reduced frequency.
  6. Noise: magnetostriction hum increases with BmB_m.

Usual values

Steel / transformerBmB_m (Wb/m²)
Hot-rolled silicon steel, distribution1.1–1.35
Hot-rolled, power transformer1.25–1.45
CRGO, distribution1.35–1.55
CRGO, power transformer1.55–1.75

So BmB_m is a compromise between a small core (high BmB_m) and low iron loss, low no-load current and low noise (low BmB_m).