Varying excitation and V curves

Short answer

Varying field excitation changes the armature current and power factor at constant load. Under-excitation gives lagging pf and high current; normal excitation yields minimum current at unity pf; over-excitation gives leading pf. V-curves plot armature current vs field current, with minima at unity pf. They show excitation for unity pf, leading kVAR supply as a synchronous condenser, and stability limits.

Explain the effect of varying excitation on armature current and power factor in a synchronous motor. Draw V curves and state their significance.

At constant load and supply voltage, the field current IfI_f of a synchronous motor controls the back emf EfE_f; this changes the armature current and the power factor, but not the speed or the active power.

Effect of varying excitation

Input power per phase P=VIacos⁡ϕP = VI_a\cos\phi is constant, so the active component Iacos⁡ϕI_a\cos\phi is constant; the tip of the IaI_a phasor moves along a line perpendicular to VV. Also Efsin⁡δE_f\sin\delta is constant, so the tip of EfE_f moves on a line parallel to VV.

          Ia3 (lead)      Ia2 (upf)
            \               |
             \              |
  ------------+-------------+--------> V
               \            |  locus of Ia tip
             Ia1 (lag)      |  (Ia cos(phi) const)
  1. Under-excitation (Ef<VE_f < V): IaI_a lags VV; it has a large lagging reactive component. Current is high, pf lagging.
  2. Increasing IfI_f: the lagging component falls, so IaI_a decreases and pf improves.
  3. Normal excitation: IaI_a is in phase with VV; current is minimum, pf = unity.
  4. Over-excitation (Ef>VE_f > V): IaI_a leads VV and grows again; pf leading. The motor now supplies reactive power to the system.

V-curves

Plotting IaI_a against IfI_f for constant power output gives V-shaped curves.

 Ia
  |F                F   F = full load
  | F              F    H = half load
  |H F          F  H    N = no load
  | H  F  F  F    H
  |N  H        H  N
  | N    H  H   N
  |   N  N  N
  +------------------- If
    lagging | leading
         upf (minima)
  • One V-curve for each load (no load, half load, full load); higher load curves lie higher and to the right.
  • The minimum point of each curve corresponds to unity pf. The line joining them is the unity pf compounding curve; points left of it are lagging, right are leading.
  • Plotting pf against IfI_f gives inverted V-curves, with peak (pf = 1) at normal excitation.

Significance of V-curves

  1. Show the field current needed for unity pf (minimum current, least copper loss) at any load.
  2. Show how much leading kVAR an over-excited motor can supply, so it can be used as a synchronous condenser for power factor correction.
  3. Show the limits of operation: the left end of each curve (very low IfI_f) approaches the stability limit, where the motor would pull out of step.
  4. Help the operator choose excitation to keep armature current within rating.
  5. Used to determine the excitation required for voltage control at substations.