Number of lamps an alternator can add

Short answer

Present load: P=400 kW, Q=300 kVAR, S=500 kVA. Maximum active power at 850 kVA with same Q: P_max = √(850² - 300²) = 795.3 kW. Additional lamp load = 795.3 - 400 = 395.3 kW. Number of 100 W lamps = 3953.

A 850 kVA, 380 V, 50 Hz 3-phase alternator delivers 400 kW to an 3-phase induction motor at a power factor of 0.8 lagging. Calculate the number of 100 W lamps which can be added to the alternator so that the alternator does not overload beyond its capacity.

Lamps are resistive (unity pf), so they add only active power; the alternator limit is its rating, 850 kVA.

Present load (induction motor)

P1=400 kWQ1=P1tan⁡ϕ=400×0.60.8=300 kVARS1=4000.8=500 kVA\begin{aligned} P_1 &= 400\ \text{kW} \\ Q_1 &= P_1\tan\phi = 400\times\frac{0.6}{0.8} = 300\ \text{kVAR} \\ S_1 &= \frac{400}{0.8} = 500\ \text{kVA} \end{aligned}

Maximum active power at 850 kVA with the same kVAR

Pmax=S2−Q12=8502−3002=795.30 kWLamp load=795.30−400=395.30 kWNumber of lamps=395.30×103100=3953\begin{aligned} P_{max} &= \sqrt{S^2 - Q_1^2} = \sqrt{850^2 - 300^2} = 795.30\ \text{kW} \\ \text{Lamp load} &= 795.30 - 400 = 395.30\ \text{kW} \\ \text{Number of lamps} &= \frac{395.30\times10^3}{100} = 3953 \end{aligned}
            S = 850 kVA
          .'|
        .'  | Q = 300 kVAR
      .'    |
    O-------+--------+
     400 kW   395.3 kW lamps

New pf of the alternator =795.3/850=0.936= 795.3/850 = 0.936 lagging.

Answer: about 3953 lamps of 100 W can be added (395.3 kW).