Design pipes AB and BC, 20,000 population, f = 0.04
Short answer
Use Darcy-Weisbach equation with f=0.04. For AB, calculated 299 mm, adopt 300 mm, velocity 1.47 m/s. For BC, calculated 245 mm, adopt 250 mm, velocity 2.12 m/s.
A part of water distribution system is shown in figure below. The average water requirement is 150 lpcd and water is distributed only from the service reservoir located at A for the population of 20,000 at the point C. Design pipes AB and BC. The minimum pressure to be maintained is 15 m and Darcy's coefficient of friction f is 0.04. Assume peak factor of 3. Calculate the velocity of water in pipes AB and BC.
[Figure: A (RL 200 m) to B (RL 170 m), length 1000 m; B to C (RL 150 m), length 500 m.]
Given data and flow
- Population at C = 20,000, 150 lpcd, peak factor 3
- lps m³/s (the full flow passes through both AB and BC)
- RL: A = 200 m (HGL = 200 m), B = 170 m, C = 150 m; m, m
- Minimum pressure 15 m (at B and C), Darcy friction factor
Formula
Pipe AB
- Available head m
- mm; adopt 300 mm
- Actual m; HGL at B m; residual head at B m (> 15 m, OK)
- Velocity m/s
Pipe BC
- Available head m
- mm; adopt 250 mm
- Actual m; HGL at C m; residual head at C m (> 15 m, OK)
- Velocity m/s
Answer: AB = 300 mm with v = 1.47 m/s; BC = 250 mm with v = 2.12 m/s. Both velocities are below 3 m/s, and the pressure at B and C stays above 15 m.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design pipes AB, BC; 160 lpcd, peak factor 3 · Water Supply Engineering, chapter 7
- Design pipes AB and BC, 75 lpcd, tank 6 m high · Water Supply Engineering, chapter 7
- Service reservoir capacity, 150,000 population · Water Supply Engineering, chapter 7
- Design pipes RA and AB; 200 lpcd, peak factor 3 · Water Supply Engineering, chapter 7
- Design pipes AB and BC, A RL 210 m, 44 and 18 lps · Water Supply Engineering, chapter 7
- Service reservoir of 30 m diameter, 1,00,000 population · Water Supply Engineering, chapter 7
- Conventional ASP design, population 1,00,000 · Sanitary Engineering, chapter 7
- Conventional ASP design, population 50,000 · Sanitary Engineering, chapter 7 · asked 2×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×