- 2070 Chaitra (old course)
Design main transmission pipes PQ and QR
Short answer
Use Hazen-Williams equation. For PQ, calculated 123.6 mm, adopt 150 mm, velocity 2.77 m/s. For QR, calculated 88.4 mm, adopt 150 mm, velocity 2.48 m/s. Recommend break pressure tank at Q.
Design suitable diameter of continuous main transmission pipe lines PQ and QR shown below. The average water requirement is 60 lpcd. The storage tank is fixed at point P of R.L. 325.0 m. The water is distributed only after the point Q for a population of 2500 and R for a population of 21000. If the minimum pressure head of water is to be 15.0 m at Q and R. Assume Hazen Williams' coefficient C as 100 and other necessary requirements if necessary.
[Figure: P (RL 325 m) to Q (RL 185 m), length 600 m; Q to R (RL 45 m), length 250 m.]
Average demand 60 lpcd. The peak factor is not stated; 3 is assumed. C = 100 and residual head = 15 m at Q and R. HGL at P = 325 m. Pipe PQ carries the demand of Q and R: (2500 + 21000) = 23,500 people, and pipe QR carries the 21,000 people at R.
- lps
- lps
Method
Use the Hazen-Williams equation in SI units:
with in m³/s, and in m. For each pipe the available head is (HGL at upstream end − ground RL of the tap − required residual head). The gradient gives the calculated diameter, the next larger commercial size is adopted, and the real head loss and residual head are then checked. Commercial sizes (nominal bore): 15, 20, 25, 32, 40, 50, 65, 80, 100, 125, 150, 200 mm and so on. Constant C = 100.
Pipe PQ
- Discharge lps, length m
- HGL at P = 325.00 m; ground RL at Q = 185 m; residual head required = 15 m
- Available head m
- Gradient
- From : mm, adopt commercial size 150 mm (raised from the head-based size because velocity would exceed 3 m/s)
- Actual m, HGL at Q = 276.21 m, residual head = 91.21 m (≥ 15 m, OK)
- Velocity m/s
Pipe QR
- Discharge lps, length m
- HGL at Q = 276.21 m; ground RL at R = 45 m; residual head required = 15 m
- Available head m
- Gradient
- From : mm, adopt commercial size 150 mm (raised from the head-based size because velocity would exceed 3 m/s)
- Actual m, HGL at R = 259.71 m, residual head = 214.71 m (≥ 15 m, OK)
- Velocity m/s
Summary
| Pipe | Q (lps) | L (m) | Calc. D (mm) | Adopted D (mm) | h_f (m) | Residual (m) | v (m/s) |
|---|---|---|---|---|---|---|---|
| PQ | 48.9583 | 600 | 123.6 | 150 | 48.79 | 91.21 | 2.77 |
| QR | 43.75 | 250 | 88.4 | 150 | 16.51 | 214.71 | 2.48 |
The static head at Q is 325 − 185 = 140 m and at R is 325 − 45 = 280 m, which is too high for ordinary pipes (and the residual heads of 91 m and 215 m are far more than needed). A break pressure tank at Q (RL 185 m) should be provided: the pressure is reduced to zero there, QR then has a static head of 140 m only, and the head available for QR becomes about 185 − 45 − 15 = 125 m, but the velocity limit of 3 m/s (125 mm gives 3.6 m/s) still requires 150 mm.
Answer: PQ = 150 mm and QR = 150 mm (with a BPT recommended at Q).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design pipes AB and BC, 75 lpcd, tank 6 m high · Water Supply Engineering, chapter 7
- Design pipes RA and AB; 200 lpcd, peak factor 3 · Water Supply Engineering, chapter 7
- Design pipes PQ, PR and RS, C = 110 · Water Supply Engineering, chapter 7
- Design pipes AB and BC, 20,000 population, f = 0.04 · Water Supply Engineering, chapter 7
- Design pipes AB, BC; 160 lpcd, peak factor 3 · Water Supply Engineering, chapter 7
- Storage tank capacity and water level, 20000 L/day · Water Supply Engineering, chapter 7 · asked 2×
- Surge and water hammer: 60 m³/s, 30 m surge tank · Hydropower Engineering, chapter 6 · asked 2×
- Proposal for a water storage tank · Communication English, chapter 6
- Continuous flow sedimentation tank particle size · Sanitary Engineering, chapter 7
- Double U-tube manometer, oil and brine pipes · Fluid Mechanics, chapter 2