Design pipes AB, BC, AD (min pressure 1.1 kg/cm2)
Short answer
Using the Hazen-Williams equation with C=100, available head, and required residual pressure of 11 m, the designed pipe diameters are AB: 25 mm, BC: 15 mm, and AD: 25 mm. All provide residual heads above 11 m and velocities below 1.1 m/s.
Design pipelines AB, BC and AD for the following pipe network. A minimum pressure of 1.1 kg/cm is required at the tap. Take Hazen Williams constant C = 100.
[Figure: reservoir at A with static water level, RL of A = 985 m. Pipe AB, L = 120 m, carries 0.35 lps and ends at B, where Tap no 1 (RL = 960 m) is located. Pipe BC, L = 150 m, carries 0.15 lps to C, where Tap no 2 (RL = 920 m) is located.]
Residual pressure at each tap = 1.1 kg/cm² = 11 m of water. Static water level at A = RL 985 m, so the HGL at A is 985 m. The figure gives only pipes AB and BC; for pipe AD the data of the companion problem is assumed (L = 160 m, Q = 0.5 lps, tap RL 940 m).
Method
Use the Hazen-Williams equation in SI units:
with in m³/s, and in m. For each pipe the available head is (HGL at upstream end − ground RL of the tap − required residual head). The gradient gives the calculated diameter, the next larger commercial size is adopted, and the real head loss and residual head are then checked. Commercial sizes (nominal bore): 15, 20, 25, 32, 40, 50, 65, 80, 100, 125, 150, 200 mm and so on. Constant C = 100.
Design
Pipe AB
- Discharge lps, length m
- HGL at A = 985.00 m; ground RL at B = 960 m; residual head required = 11 m
- Available head m
- Gradient
- From : mm, adopt commercial size 25 mm
- Actual m, HGL at B = 978.62 m, residual head = 18.62 m (≥ 11 m, OK)
- Velocity m/s
Pipe BC
- Discharge lps, length m
- HGL at B = 978.62 m; ground RL at C = 920 m; residual head required = 11 m
- Available head m
- Gradient
- From : mm, adopt commercial size 15 mm
- Actual m, HGL at C = 958.63 m, residual head = 38.63 m (≥ 11 m, OK)
- Velocity m/s
Pipe AD
- Discharge lps, length m
- HGL at A = 985.00 m; ground RL at D = 940 m; residual head required = 11 m
- Available head m
- Gradient
- From : mm, adopt commercial size 25 mm
- Actual m, HGL at D = 968.53 m, residual head = 28.53 m (≥ 11 m, OK)
- Velocity m/s
Summary
| Pipe | Q (lps) | L (m) | Calc. D (mm) | Adopted D (mm) | h_f (m) | Residual (m) | v (m/s) |
|---|---|---|---|---|---|---|---|
| AB | 0.35 | 120 | 21.3 | 25 | 6.38 | 18.62 | 0.71 |
| BC | 0.15 | 150 | 12.6 | 15 | 19.99 | 38.63 | 0.85 |
| AD | 0.5 | 160 | 21.5 | 25 | 16.47 | 28.53 | 1.02 |
Maximum static head: B = 985 − 960 = 25 m, D = 45 m and C = 985 − 920 = 65 m. Pipe BC must therefore be of a class that can bear at least 65 m (about 0.65 MPa), e.g. GI medium or HDPE PN 10, while AB can be a lower class.
Answer: AB = 25 mm, BC = 15 mm, AD = 25 mm (GI), all giving residual head above 11 m and velocity below 1.1 m/s.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design pipelines AB, BC, AD; 1 kg/cm2 at tap · Water Supply Engineering, chapter 7
- Design pipes AB and BC, source RL 1050 m · Water Supply Engineering, chapter 7
- Design pipelines AB and BC, C = 100, 10 m head · Water Supply Engineering, chapter 7
- Hardy-Cross network discharge AB, BC, AD, CD · Water Supply Engineering, chapter 7
- Design pipes AB, BC and AC, C = 110 · Water Supply Engineering, chapter 7
- Design pipes AB and BC, source RL 180 m · Water Supply Engineering, chapter 7