Design pipelines AB, BC, AD; 1 kg/cm2 at tap

Short answer

Use Hazen-Williams equation with C=100. Pipe AB (0.25 lps, 120 m) adopts 20 mm, pipe BC (0.1 lps, 150 m) adopts 15 mm, pipe AD (0.5 lps, 160 m) adopts 25 mm. Residual heads exceed 10 m at all taps.

Design pipelines AB, BC and AD for the following pipe network. A minimum pressure of 1 kg/cm2^2 is required at the tap. Take Hazen William constant C = 100.

[Figure: Source RL = 985 m at A. AB: L = 120 m, 0.25 lps, to B with Tap no. 1 (RL = 960 m). BC: L = 150 m, 0.1 lps, to C with Tap no. 2 (RL = 920 m). AD: L = 160 m, 0.5 lps, to D with Tap no. 3 (RL = 940 m).]

Residual pressure = 1 kg/cm² = 10 m; C = 100. HGL at A = 985 m. Discharges as given: AB = 0.25 lps, BC = 0.10 lps, AD = 0.50 lps.

Method

Use the Hazen-Williams equation in SI units:

hf=10.67 L Q1.852C1.852D4.87h_f = \frac{10.67\,L\,Q^{1.852}}{C^{1.852}D^{4.87}}

with QQ in m³/s, LL and DD in m. For each pipe the available head is (HGL at upstream end − ground RL of the tap − required residual head). The gradient S=H/LS = H/L gives the calculated diameter, the next larger commercial size is adopted, and the real head loss and residual head are then checked. Commercial sizes (nominal bore): 15, 20, 25, 32, 40, 50, 65, 80, 100, 125, 150, 200 mm and so on. Constant C = 100.

Pipe AB

  • Discharge Q=0.250Q = 0.250 lps, length L=120L = 120 m
  • HGL at A = 985.00 m; ground RL at B = 960 m; residual head required = 10 m
  • Available head H=985.00−960−10=15.00H = 985.00 - 960 - 10 = 15.00 m
  • Gradient S=H/L=15.00/120=0.12500S = H/L = 15.00/120 = 0.12500
  • From hf=10.67 L Q1.852C1.852D4.87h_f = \dfrac{10.67\,L\,Q^{1.852}}{C^{1.852}D^{4.87}}: Dcalc=18.5D_{calc} = 18.5 mm, adopt commercial size 20 mm
  • Actual hf=10.146h_f = 10.146 m, HGL at B = 974.85 m, residual head = 14.85 m (≥ 10 m, OK)
  • Velocity v=Q/A=0.80v = Q/A = 0.80 m/s

Pipe BC

  • Discharge Q=0.100Q = 0.100 lps, length L=150L = 150 m
  • HGL at B = 974.85 m; ground RL at C = 920 m; residual head required = 10 m
  • Available head H=974.85−920−10=44.85H = 974.85 - 920 - 10 = 44.85 m
  • Gradient S=H/L=44.85/150=0.29902S = H/L = 44.85/150 = 0.29902
  • From hf=10.67 L Q1.852C1.852D4.87h_f = \dfrac{10.67\,L\,Q^{1.852}}{C^{1.852}D^{4.87}}: Dcalc=10.9D_{calc} = 10.9 mm, adopt commercial size 15 mm
  • Actual hf=9.434h_f = 9.434 m, HGL at C = 965.42 m, residual head = 45.42 m (≥ 10 m, OK)
  • Velocity v=Q/A=0.57v = Q/A = 0.57 m/s

Pipe AD

  • Discharge Q=0.500Q = 0.500 lps, length L=160L = 160 m
  • HGL at A = 985.00 m; ground RL at D = 940 m; residual head required = 10 m
  • Available head H=985.00−940−10=35.00H = 985.00 - 940 - 10 = 35.00 m
  • Gradient S=H/L=35.00/160=0.21875S = H/L = 35.00/160 = 0.21875
  • From hf=10.67 L Q1.852C1.852D4.87h_f = \dfrac{10.67\,L\,Q^{1.852}}{C^{1.852}D^{4.87}}: Dcalc=21.4D_{calc} = 21.4 mm, adopt commercial size 25 mm
  • Actual hf=16.474h_f = 16.474 m, HGL at D = 968.53 m, residual head = 28.53 m (≥ 10 m, OK)
  • Velocity v=Q/A=1.02v = Q/A = 1.02 m/s

Summary

PipeQ (lps)L (m)Calc. D (mm)Adopted D (mm)h_f (m)Residual (m)v (m/s)
AB0.2512018.52010.1514.850.80
BC0.115010.9159.4345.420.57
AD0.516021.42516.4728.531.02

Static head is highest at C (985 − 920 = 65 m), so the pipes BC (and AB feeding it) must be of a class suitable for at least 65 m.

Answer: AB = 20 mm, BC = 15 mm, AD = 25 mm.