- Asked 2/16
- 2071 Magh · 8 marks
- 2075 Bhadra · 8 marks
Carrier current and bus-bar protection
Short answer
Carrier current protection sends a high-frequency signal over the power line itself via coupling capacitors and line traps to provide fast unit protection. A blocking scheme trips only for internal faults. Bus-bar protection commonly uses differential relays: CT secondaries of all connected circuits are paralleled; the relay trips all breakers on the bus for any non-zero sum current.
Explain the following types of protection with suitable diagrams: i) Carrier current protection ii) Bus-bar protection.
i) Carrier current protection
Carrier current protection is a unit protection for long transmission lines in which information about the currents at both ends is sent over the power line itself using a high-frequency carrier signal (50–500 kHz). It allows high-speed, simultaneous tripping at both ends for faults anywhere on the line, where pilot wires would be too long.
Equipment at each end
- Transmitter and receiver (carrier set) producing and detecting the HF signal.
- Coupling capacitor: connects the carrier set to the HV line and blocks power-frequency voltage.
- Line trap (wave trap): a parallel LC circuit tuned to the carrier frequency, in series with the line; it confines the carrier to the protected section and passes 50 Hz.
- Relays: directional or distance relays and a fault detector.
Bus A Bus B
│ CB Line trap ═══════ Line ═══════ Line trap CB │
├──□───[LC]──┬────────────────────────┬──[LC]───□──┤
│ │
Coupling cap. Coupling cap.
│ │
Transmitter/Receiver Transmitter/Receiver
│ │
Relays ───── trip ───── Relays
Directional comparison (blocking) scheme
- Directional relays at both ends see the fault direction.
- For an internal fault, power flows into the line at both ends; both relays see "forward" and no blocking carrier is sent; both breakers trip.
- For an external fault, the relay at the end nearest the fault sees power flowing out of the line; it starts its transmitter and sends a blocking signal to the remote end, which prevents tripping.
Phase comparison scheme: the phase of currents at the two ends is compared via the carrier; in-phase (internal fault) → trip; 180° out of phase (through fault) → block.
Advantages: fast (1–3 cycles), simultaneous tripping at both ends, permits high-speed auto reclosing, no separate communication channel needed; the carrier can also be used for telephony and telemetry.
ii) Bus-bar protection
Bus-bar protection detects faults on the busbars of a substation and trips all breakers connected to the faulty bus section. Busbar faults are rare but severe, so the scheme must be fast and very stable for external faults.
Methods
- Back-up protection by remote relays: the bus is cleared by the time-delayed relays of the connected circuits; simple but slow.
- Fault bus (frame leakage) protection: used for metal-clad switchgear; the frame is insulated from earth and earthed through a single CT and relay; an earth fault to the frame trips all breakers.
- Differential protection (most common): based on Kirchhoff's current law: the sum of currents entering a healthy bus is zero.
Feeder1 Feeder2 Feeder3 Source
│CT │CT │CT │CT
════╪════════════╪══════════╪═════════╪════ Bus
│ │ │ │
└─────┬──────┴────┬─────┴────┬────┘
│ CT secondaries paralleled
└────────[ R ]─────────┘
differential relay
- CTs of the same ratio are placed in every circuit connected to the bus, and their secondaries are connected in parallel with the relay.
- Normal load or external fault: ΣI = 0, so no current flows in the relay.
- Bus fault: all circuits feed the fault; ΣI = total fault current, and the relay trips all breakers on that bus.
- High impedance differential scheme is widely used: a high-resistance relay with a stabilising resistor prevents false tripping when a CT saturates during a heavy external fault. Biased (percentage) differential relays are also used.
- Large stations divide the bus into zones with separate protection, plus a check zone to avoid false trips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Ring bus rearrangement and zones · Switchgear and Protection, chapter 1
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Prospective current, cut-off current, time delay fuse · Switchgear and Protection, chapter 3
- Balanced circulating current: 10 kV alternator · Switchgear and Protection, chapter 7
- Cut-off and time-current characteristics of fuse · Switchgear and Protection, chapter 3
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×
- High voltage bus bar types · Power Plant Design, chapter 4
- Reactor function and ring bus-bar scheme · Power Plant Equipment, chapter 4