- 2079 Shrawan · 8 marks
High voltage bus bar types
Short answer
Different types include single bus, sectionalised single, main and transfer, double bus, double bus double breaker, breaker-and-a-half, and ring bus. Main and transfer bus allows feeder breaker maintenance without outage using a bus coupler; advantages: low cost, simple layout. Disadvantages: main bus fault causes full outage, only one bypass at a time, complex switching.
Write down the different types of high voltage bus bar with appropriate line diagram. Write the advantages and disadvantages of main and transfer bus bar.
A busbar is a conductor in a switchyard to which incoming and outgoing circuits are connected. Its arrangement decides reliability, flexibility of maintenance and cost.
Types of HV busbar arrangement
1. Single bus: all circuits on one bus. Cheap, but any bus fault or maintenance shuts down everything.
L1 L2 L3
| | |
[CB] [CB] [CB]
==+=====+=====+== bus
[CB] [CB]
| |
G1 T1
2. Sectionalised single bus: bus split by a bus-section breaker; a fault affects only one section.
3. Main and transfer bus: each circuit normally on the main bus; a bus coupler (transfer) breaker can take over any one feeder whose breaker is under maintenance.
Main bus ===+========+========+===
| | |
[CB] [CB] [BC] coupler
| | |
Transfer bus ---+--/ ----+--/ ----+---
| bypass isolator
L1 L2
4. Double bus (double bus single breaker): two main buses; each circuit can be connected to either bus through isolators, with a bus coupler.
Bus-1 ===+=========+=====+===
| | [BC]
Bus-2 ===+=========+=====+===
| (isolators)
[CB] [CB]
L1 L2
5. Double bus double breaker: each circuit has two breakers, one to each bus. Very reliable, costly.
6. Breaker-and-a-half (one-and-half breaker): three breakers for two circuits between two buses. Common at 220 kV and 400 kV.
7. Ring (mesh) bus: breakers form a closed loop; each circuit between two breakers.
Main and transfer bus: advantages
- Any feeder breaker can be taken out for maintenance without interrupting that feeder (it is fed through the transfer bus and bus coupler).
- Low cost compared with double bus or breaker-and-a-half: only one extra breaker.
- Simple layout and protection.
- Suitable for 33–132 kV substations.
Main and transfer bus: disadvantages
- A fault on the main bus or its maintenance shuts down the whole substation (no second main bus).
- Only one breaker at a time can be bypassed.
- Protection of the transferred feeder must be switched to the bus coupler, so switching is more complex and error-prone.
- More isolators and switching operations; needs interlocking.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design: 200 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 14×
- Design: 230 m head plant, 20 km line · Power Plant Design, chapter 4 · asked 14×
- Design: 250 m head plant, 35 km line · Power Plant Design, chapter 4 · asked 12×
- Design: 230 m head plant, 45 km line · Power Plant Design, chapter 4 · asked 12×
- Design: 120 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Design: 150 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Carrier current and bus-bar protection · Switchgear and Protection, chapter 7 · asked 2×
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×