Minimum TMS of relay A (16000 A fault)

Short answer

Relay B: PSM=16000/(1.25×800)=16, t=0.2×2=0.4 s. Required t_A includes breaker time 0.2 s and errors ±0.15 s each: t_A=0.4+0.2+0.15+0.15=0.9 s. Relay A pickup 1600 A, PSM=10, t(TMS=1)=3 s, so minimum TMS_A=0.9/3=0.3.

As shown in figure, the relay at B has a plug setting of 125% and TMS of 0.2. The circuit breakers take 0.20 sec to clear the fault and the relay error in each case is 0.15 sec. For a plug setting of 200% on the relay A, determine the minimum TMS on that relay for it not to operate before the circuit breaker at B has cleared the fault. A relay operating time curve is shown in table. [Figure: Bus A – CB – CT 800/5 with relay R2 – bus B – CB – CT 800/5 with relay R1 – fault F, If = 16000 A.]

IDMT characteristic:

PSM23.556.5810121416
Operating Time (sec)106543.1532.92.52

Relay A is the back-up for relay B. It must not trip until relay B has operated and breaker B has cleared the fault, allowing for errors in both relays.

Data: CT 800/5 for both; relay B: PS 125%, TMS 0.2; relay A: PS 200%; If = 16000 A; CB time 0.2 s; relay error 0.15 s each.

Relay B

Pick-up = 1.25 × 800 = 1000 A
PSM = 16000/1000 = 16 → t(TMS=1) = 2 s
t_B = 0.2 × 2 = 0.4 s

Required time of relay A

Relay B may be 0.15 s slow and relay A may be 0.15 s fast, so:

t_A = t_B + CB time + error(B) + error(A)
    = 0.4 + 0.2 + 0.15 + 0.15 = 0.9 s

TMS of relay A

Pick-up = 2.0 × 800 = 1600 A
PSM = 16000/1600 = 10 → t(TMS=1) = 3 s
TMS_A = 0.9 / 3 = 0.3

Answer: minimum TMS of relay A = 0.3 (operating time 0.9 s). Any smaller TMS could let relay A trip before breaker B has cleared the fault.