- 2081 Baisakh · 10 marks
Column 350x550 with major axis moment
Short answer
Provide 8-16 mm bars (0.84%) and 8 mm ties @ 250 mm c/c. The column is short; uniaxial moment capacity 231.7 kN·m exceeds the design moment 200 kN·m.
Design longitudinal and transverse reinforcement in a rectangular RC column of size 350 mm x 550 mm subjected to a factored axial load of 900 kN and moment equal to 200 kN-m with respect to the major axis. Take unsupported length of 3 m and effective length of 3.6 m. Use M25 concrete and Fe415 grade steel.
Data and assumptions
- Column 350 mm (width ) × 550 mm (depth ); kN; MPa, MPa. Clear cover 40 mm (IS 456 cl. 26.4.2.1), 8 mm ties.
- Moment about major axis: = 200 kN·m.
- Sizes are given as with ; moments act about the major axis (depth ) and about the minor axis (depth ).
Slenderness
| Axis | (mm) | Dimension (mm) | dim | Type |
|---|---|---|---|---|
| x-x (about major) | 3600 | 550 | 6.55 | short |
| y-y (about minor) | 3600 | 350 | 10.29 | short |
| Both ratios are below 12, so the column is short; no additional moment is required. |
Minimum eccentricity (cl. 25.4)
- About x-x: mm (min. 20 mm); adopt 24.3 mm; kN·m
- About y-y: mm (min. 20 mm); adopt 20.0 mm; kN·m
Design moments
- Design moments: kN·m (not less than the minimum-eccentricity values).
Longitudinal reinforcement
Bars are chosen so that lies between 0.8% (minimum) and 4% (practical maximum; IS 456 cl. 26.5.3.1 allows 6%). The uniaxial capacities , at are read from the SP-16 interaction charts for rectangular sections; here they are computed by strain compatibility with the IS 456 stress block and the design stress-strain curve of steel (same basis as the charts), with effective cover .
| Trial | (%) | (kN·m) | required | Ratio | |
|---|---|---|---|---|---|
| 8-16 φ | 0.84 | 0.102 | 231.7 | 200.0 | 0.863 ok |
Check
kN·m kN·m. Minimum eccentricity about the minor axis: kN·m kN·m. Both are satisfied; the section is safe.
Provide 8-16 mm bars ( mm², ), within 0.8% to 4%.
Lateral ties
- Diameter mm → provide 8 mm.
- Pitch (least lateral dimension, , 300 mm) mm → provide 8 mm ties @ 250 mm c/c.
Detailing
CROSS-SECTION 350 x 550
+-------------------------+
| o o o |
| |
| |
| |
| |
| o o |
| |
| |
| |
| |
| o o o |
+-------------------------+
o = 16 mm bars, ties 8 mm @ 250 c/c
Answer: 350 × 550 mm column with 8-16 mm longitudinal bars () and 8 mm ties @ 250 mm c/c.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Column 350x350, 1440 kN, ductile detailing · Design of RCC Structure, chapter 10 · asked 2×
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Short column 300x500, 2000 kN, M30 · Design of RCC Structure, chapter 10
- Short column 300x400, 1400 kN · Design of RCC Structure, chapter 10 · asked 2×
- Rectangular column with working-load moment · Design of RCC Structure, chapter 10
- Short column 350x500, M30, 1500 kN · Design of RCC Structure, chapter 10 · asked 2×
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Box deodar column, 60 mm planks, 350 kN · Design of Steel and Timber Structure, chapter 11
- Timber column under axial load and bending · Design of Timber and Masonry Structures, chapter 3
- Select Sal column, 200 kN + 30 kNm · Design of Steel and Timber Structure, chapter 11