Short column 300x400, 1400 kN
Short answer
The 300x400 section is inadequate; revise to 400x500. Use 14-20 mm bars (p=2.20%) and 8 mm ties @200 mm c/c outside the confining zone; provide special confining hoops @75 mm c/c over 500 mm at each end.
Determine the longitudinal and transverse reinforcements in a short RC column subjected to factored axial load of 1400 kN and factored moment of 200 kN-m and of 110 kNm. The size of the column is 300 mm x 400 mm and unsupported length of 3 m. Adopt M20 concrete and Fe500 grade (TMT) bars. Also, do the ductile detailing of transverse reinforcements.
Check of the given section 300 × 400 mm
Even with the largest practical steel (for example 14-25 mm bars, ), the interaction ratio is 1.34 > 1 for kN with the given moments. The given section is therefore too small, and the column must be enlarged.
Data and assumptions
- The section given in the question (300 × 400 mm) is checked first and found inadequate (see above), so a revised section 400 × 500 mm is designed.
- Column 400 mm (width ) × 500 mm (depth ); kN; MPa, MPa. Clear cover 40 mm (IS 456 cl. 26.4.2.1), 8 mm ties.
- Moments: about major axis (x-x) = 200 kN·m; about minor axis (y-y) = 110 kN·m.
- Effective length is taken equal to the unsupported length, 3 m.
Slenderness
| Axis | (mm) | Dimension (mm) | dim | Type |
|---|---|---|---|---|
| x-x (about major) | 3000 | 500 | 6.00 | short |
| y-y (about minor) | 3000 | 400 | 7.50 | short |
| Both ratios are below 12, so the column is short; no additional moment is required. |
Minimum eccentricity (cl. 25.4)
- About x-x: mm (min. 20 mm); adopt 22.7 mm; kN·m
- About y-y: mm (min. 20 mm); adopt 20.0 mm; kN·m
Design moments
- Design moments: kN·m, kN·m (not less than the minimum-eccentricity values).
Longitudinal reinforcement
Bars are chosen so that lies between 0.8% (minimum) and 4% (practical maximum; IS 456 cl. 26.5.3.1 allows 6%). The uniaxial capacities , at are read from the SP-16 interaction charts for rectangular sections; here they are computed by strain compatibility with the IS 456 stress block and the design stress-strain curve of steel (same basis as the charts), with effective cover .
| Trial | (%) | ||||||
|---|---|---|---|---|---|---|---|
| 8-25 φ | 1.96 | 0.121 | 283.1 | 210.2 | 0.432 | 1.39 | 1.025 ✗ |
| 20-16 φ | 2.01 | 0.112 | 283.5 | 212.0 | 0.428 | 1.38 | 1.022 ✗ |
| 14-20 φ | 2.20 | 0.116 | 292.9 | 234.0 | 0.411 | 1.35 | 0.958 ✓ |
Check
kN , so (IS 456 cl. 39.6; linear between 1.0 at 0.2 and 2.0 at 0.8).
The interaction condition is satisfied; the section is safe.
Provide 14-20 mm bars ( mm², ), within 0.8% to 4%.
Lateral ties
- Diameter mm → provide 8 mm.
- Pitch by IS 456 (least lateral dimension, , 300 mm) mm. For ductile detailing, IS 13920 limits the spacing outside the confining zone to half the least lateral dimension = 200 mm → provide 8 mm ties @ 200 mm c/c outside .
Ductile detailing of transverse steel (IS 13920)
- Special confining length at each end: mm → provide 500 mm from each joint face.
- Spacing of hoops within : mm, and not less than 75 mm → 100 mm c/c.
- The bars are about 95 mm apart (more than 75 mm), so the intermediate bars are held by cross-ties in addition to the rectangular hoop.
- Area of one hoop leg: , where is the longer c/c distance between adjacent hoop legs or cross-ties (not more than 300 mm), here mm; mm² (core measured to the outside of the hoop); mm². mm²
- An 8 mm leg gives 50.3 mm² 42.2 mm², so 8 mm hoops and cross-ties @ 100 mm c/c are adequate. Hoops have 135° hooks with a 6φ (≥ 65 mm) extension.
- Outside : 8 mm ties @ 200 mm c/c ( mm).
Detailing
CROSS-SECTION 400 x 500
+-------------------------+
| o o o o |
| |
| |
| o o |
| |
| o o |
| |
| o o |
| |
| |
| o o o o |
+-------------------------+
o = 20 mm bars; hoop + cross-ties
8 mm @ 100 c/c over 500 mm at each end,
8 mm @ 200 c/c in the middle region
Answer: 400 × 500 mm column with 14-20 mm longitudinal bars (); 8 mm hoops with cross-ties @ 100 mm c/c over 500 mm at each end, and 8 mm ties @ 200 mm c/c in the middle region.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Column 350x350, 1440 kN, ductile detailing · Design of RCC Structure, chapter 10 · asked 2×
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Short column 300x500, 2000 kN, M30 · Design of RCC Structure, chapter 10
- Column 350x550 with major axis moment · Design of RCC Structure, chapter 10
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Short column 35x45 cm, 1800 kN · Design of RCC Structure, chapter 10
- Footing for 400x300 column, reversible moment · Design of RCC Structure, chapter 11
- Select Sal column, 200 kN + 30 kNm · Design of Steel and Timber Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Check 25 cm x 25 cm Sal column, 200 kN + 20 kNm · Design of Steel and Timber Structure, chapter 11
- Corner stresses of 400 x 800 column (200 kN) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×