Isolated footing 500x500, 1600 kN
Short answer
Provide a 3.8 m × 3.8 m square footing, depth 700 mm (d = 640 mm). Factored upward pressure 166.2 kN/m² yields bending moment 859.7 kN·m per direction; use 12 mm bars at 130 mm c/c both ways. One‑way and punching shear are safe, and 8‑20 mm dowels transfer column load.
Design an isolated footing for a column of size 500 mm x 500 mm, and carrying a service axial load of 1600 kN. Assume soil with an allowable bearing capacity of 125 kN/m at a depth of 1.25 m below ground. Assume Fe500 TMT steel for both column and footing, and M25 grade concrete for the footing and M25 grade concrete for the column. Make construction drawings in plan and elevation.
Data and assumptions
- Column 500 mm × 500 mm (long side mm along the footing length); footing concrete M25, steel Fe500; column concrete M25; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 125 kN/m² at 1.25 m depth.
- The foundation depth of 1.25 m does not enter the calculation directly; the weight of the footing and backfill is taken as 10% of the column load.
- Column bars assumed 8-20 mm (not given).
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 14.44 m² 14.08 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 859.7 | 3192 | 12 mm @ 130 c/c | 3306 |
| Along (width ) | 859.7 | 3192 | 12 mm @ 130 c/c | 3306 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M25, deformed bars): 12 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1600 mm along , 1600 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 22.50 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 2812 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1250 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 24 = 626 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN (3.8 m x 3.8 m)
+------------------------------------+
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | +----------+ | | | |
|--+---+---+-| column |--+---+---+-|
| | | | +----------+ | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
+------------------------------------+
| = bars along B, - = bars along L: 12 mm @ 130 c/c both ways
ELEVATION
| column |
| |
+---------------+----------+---------------+
| (dowels) | D = 700 mm
| o o o o o o o o o o o o o | bottom mesh, 50 mm cover
+------------------------------------------+
<---------------- 3800 mm ----------------->
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.8 m × 3.8 m × 700 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 500x500 with moment, M25 · Design of RCC Structure, chapter 11
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 1250 kN column load, depth 1.8 m · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Allowable load of 400 mm pile, layered soil · Foundation Engineering, chapter 8
- Footing size from plate load test curve · Foundation Engineering, chapter 6
- Rectangular footing size, 6000 kN · Foundation Engineering, chapter 6