Isolated footing 500x500 with moment, M25

Short answer

Square footing 3.1 m × 3.1 m, overall depth 650 mm (effective 590 mm). Main reinforcement 16 mm @ 185 mm c/c both ways; one-way and punching shear are within limits.

Design an isolated footing to carry a column load of 1300 kN and BM of 100 kN-m from both axes of column. Column is 500 mm x 500 mm in size with 25 mm diameter longitudinal steel. The bearing capacity of soil is 220 kN/m2^2. Consider depth of foundation as 1.70 m. Take unit weight of soil as 18.5 kN/m3^3. Use M25 grade concrete and Fe415 steel.

Data and assumptions

  • Column 500 mm × 500 mm (long side a=500a=500 mm along the footing length); footing concrete M25, steel Fe415; column concrete M25; column bars 8-25 mm.
  • Service load P=1300P = 1300 kN, service moment M=100M = 100 kN·m (about the other axis also 100 kN·m).
  • Allowable (safe) bearing capacity of soil = 220 kN/m² at 1.7 m depth, soil unit weight 18.5 kN/m³.
  • Loads are service loads; moments of 100 kN·m act about both axes, so a square footing is used.
  • Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth d=D−60d = D - 60 mm (cover + half bar). Load factor 1.5.

Size of footing

Net safe bearing capacity = q−γDf=220−18.5×1.7=188.55q - \gamma D_f = 220 - 18.5 \times 1.7 = 188.55 kN/m² (this takes care of the weight of footing and backfill).

Areq=Pqnet=1300.0188.55=6.89 m2A_{req} = \frac{P}{q_{net}} = \frac{1300.0}{188.55} = 6.89\ \text{m}^2

Eccentricity e=M/P=100.0/1300.0=0.077e = M/P = 100.0/1300.0 = 0.077 m (and 0.077 m in the other direction), which is less than L/6L/6, so there is no tension under the base. The size is chosen so that

qmax=PBL(1+6eL+6eyB)≤qaq_{max} = \frac{P}{BL}\left(1 + \frac{6e}{L} + \frac{6e_y}{B}\right) \le q_a

Try L×B=3.1×3.1L \times B = 3.1 \times 3.1 m (A=9.61A = 9.61 m²): qmax=175.6q_{max} = 175.6 kN/m² ≤188.6\le 188.6 and qmin=95.0q_{min} = 95.0 kN/m² >0> 0. Safe.

Factored soil pressure

Pu=1.5×1300.0=1950.0P_u = 1.5 \times 1300.0 = 1950.0 kN, Mu=150.0M_u = 150.0 kN·m. pu=PuBL(1±6eL±6eyB)p_u = \dfrac{P_u}{BL}\left(1 \pm \dfrac{6e}{L} \pm \dfrac{6e_y}{B}\right): pu,max=263.3p_{u,max} = 263.3 kN/m², pu,min=142.5p_{u,min} = 142.5 kN/m² (average 202.9 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.

Bending moments and reinforcement

Cantilever projections from the column face: along LL: (3100−500)/2=1300(3100 - 500)/2 = 1300 mm; along BB: (3100−500)/2=1300(3100 - 500)/2 = 1300 mm. With the maximum pressure assumed over the cantilever (conservative): Mu,L=689.8M_{u,L} = 689.8 kN·m, Mu,B=689.8M_{u,B} = 689.8 kN·m. Required depth for flexure: Mu,lim=0.138fckbd2M_{u,lim} = 0.138 f_{ck} b d^2 is far larger than the moment for d=590d = 590 mm, so the depth is governed by shear (one-way or punching). Trial D=650D = 650 mm, d=590d = 590 mm, found by the shear checks below.

Ast=0.5fckfy[1−1−4.6Mufckbd2]bdA_{st} = \dfrac{0.5 f_{ck}}{f_y}\left[1 - \sqrt{1 - \dfrac{4.6 M_u}{f_{ck} b d^2}}\right] b d; minimum steel = 0.12% of bDbD.

DirectionMuM_u (kN·m)AstA_{st} req (mm²)ProvideAstA_{st} prov (mm²)
Along LL (width BB)689.8334116 mm @ 185 c/c3369
Along BB (width LL)689.8334116 mm @ 185 c/c3369

Check for one-way shear (at distance dd from the column face)

  • Along LL side: Vu=579.6V_u = 579.6 kN, τv=VuBd=0.317\tau_v = \dfrac{V_u}{B d} = 0.317 MPa; pt=0.184%p_t = 0.184\%, τc=0.319\tau_c = 0.319 MPa (IS 456 Table 19, SP 16 formula). τv<τc\tau_v < \tau_c, safe.
  • Along BB side: Vu=579.6V_u = 579.6 kN, τv=0.317\tau_v = 0.317 MPa; pt=0.184%p_t = 0.184\%, τc=0.319\tau_c = 0.319 MPa. Safe.

Check for two-way (punching) shear (at d/2d/2 from the column face)

  • Perimeter bo=2[(a+d)+(c+d)]=2[(500+590)+(500+590)]=4360b_o = 2[(a + d) + (c + d)] = 2[(500+590) + (500+590)] = 4360 mm
  • Vu=Pu−pu(a+d)(c+d)=1950.0−202.9×1.090×1.090=1708.9V_u = P_u - p_u (a+d)(c+d) = 1950.0 - 202.9 \times 1.090 \times 1.090 = 1708.9 kN (average pressure; the effect of moment transfer is neglected).
  • τv=Vubod=0.664\tau_v = \dfrac{V_u}{b_o d} = 0.664 MPa; ks=0.5+βc=1.00k_s = 0.5 + \beta_c = 1.00, τc′=ks×0.25fck=1.250\tau_c' = k_s \times 0.25\sqrt{f_{ck}} = 1.250 MPa. τv<τc′\tau_v < \tau_c', safe.

Development length

Ld=0.87fyϕ4τbdL_d = \dfrac{0.87 f_y \phi}{4\tau_{bd}}, τbd=2.24\tau_{bd} = 2.24 MPa (M25, deformed bars): 16 mm bars (both directions) → Ld=645L_d = 645 mm. Available length from column face (less 50 mm end cover): 1250 mm along LL, 1250 mm along BB. Satisfied in both directions.

Bearing stress and transfer of load from column

Column area A2=500×500=0.250A_2 = 500\times500 = 0.250 m². Bearing stress =Pu/A2=7.80= P_u/A_2 = 7.80 MPa. Permissible bearing stress: column concrete 0.45fck=11.250.45 f_{ck} = 11.25 MPa; footing concrete 0.45fckA1/A20.45 f_{ck}\sqrt{A_1/A_2} with A1/A2≤2\sqrt{A_1/A_2} \le 2 gives up to 22.50 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 2812 kN ≥\ge Pu=1950P_u = 1950 kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1250 mm²: use 8 bars of 25 mm (3927 mm²) as dowels, same as column bars. Dowel length in compression Ldc=0.87fyϕ4×1.25 τbd=806L_{dc} = \dfrac{0.87 f_y\phi}{4 \times 1.25\,\tau_{bd}} = 806 mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 32 = 568 mm <Ldc< L_{dc}; dowels are bent at the bottom with 90° bends.

Detailing

PLAN                      ELEVATION
+------------------+      col
| #  #  #  #  #  # |      | |
| #  +------+  #  # |     _|_|__
| #  | col  |  #  # |    |_____|  <- D = 650 mm
| #  +------+  #  # |    bars both ways
| #  #  #  #  #  # |
+------------------+
 L = 3.1 m, B = 3.1 m
  • Bottom mesh: 16 mm @ 185 c/c along LL (lower layer), 16 mm @ 185 c/c along BB (upper layer), 50 mm clear cover; dowels 8-25 mm.

Answer: Footing 3.1 m × 3.1 m × 650 mm thick; 16 mm @ 185 c/c along the length and 16 mm @ 185 c/c along the width.

✓ Answer checked by Claude Opus 5.5 (high effort)