Short column 300x450 with ductile detailing
Short answer
Assuming M25 and Fe500, use 10-25 mm bars (p=3.64%) and 8 mm ties @150 mm c/c outside the confining zone; special confining hoops @75 mm c/c over 500 mm at each end.
Design a short RC column with following data: Unsupported length = 3.0 m; Factored load, = 1550 kN; Factored moments: = 130 kN.m, = 90 kN.m; Size of column = 300 x 450 mm. Do ductile detailing for transverse steel.
Data and assumptions
- Column 300 mm (width ) × 450 mm (depth ); kN; MPa, MPa. Clear cover 40 mm (IS 456 cl. 26.4.2.1), 8 mm ties.
- Moments: about major axis (x-x) = 130 kN·m; about minor axis (y-y) = 90 kN·m.
- Grades of concrete and steel are not given; M25 and Fe500 are assumed.
- Sizes are given as with ; moments act about the major axis (depth ) and about the minor axis (depth ).
Slenderness
| Axis | (mm) | Dimension (mm) | dim | Type |
|---|---|---|---|---|
| x-x (about major) | 3000 | 450 | 6.67 | short |
| y-y (about minor) | 3000 | 300 | 10.00 | short |
Both ratios are below 12, so the column is short; no additional moment is required.
Minimum eccentricity (cl. 25.4)
- About x-x: mm (min. 20 mm); adopt 21.0 mm; kN·m
- About y-y: mm (min. 20 mm); adopt 20.0 mm; kN·m
Design moments
- Design moments: kN·m, kN·m (not less than the minimum-eccentricity values).
Longitudinal reinforcement
Bars are chosen so that lies between 0.8% (minimum) and 4% (practical maximum; IS 456 cl. 26.5.3.1 allows 6%). The uniaxial capacities , at are read from the SP-16 interaction charts for rectangular sections; here they are computed by strain compatibility with the IS 456 stress block and the design stress-strain curve of steel (same basis as the charts), with effective cover .
| Trial | (%) | ||||||
|---|---|---|---|---|---|---|---|
| 8-25 φ | 2.91 | 0.134 | 203.7 | 114.1 | 0.526 | 1.54 | 1.194 ✗ |
| 14-20 φ | 3.26 | 0.129 | 214.7 | 129.0 | 0.497 | 1.50 | 1.056 ✗ |
| 10-25 φ | 3.64 | 0.134 | 233.4 | 142.6 | 0.469 | 1.45 | 0.942 ✓ |
Check
kN , so (IS 456 cl. 39.6; linear between 1.0 at 0.2 and 2.0 at 0.8).
The interaction condition is satisfied; the section is safe.
Provide 10-25 mm bars ( mm², ), within 0.8% to 4%.
Lateral ties
- Diameter mm → provide 8 mm.
- Pitch (least lateral dimension, , 300 mm) mm by IS 456. IS 13920 reduces this to 150 mm outside (see below), so 8 mm ties @ 150 mm c/c are provided.
Ductile detailing of transverse steel (IS 13920)
- Special confining length at each end: mm → provide 500 mm from each joint face.
- Spacing of hoops within : mm and not less than 75 mm → 75 mm c/c.
- Area of one hoop leg (bar): , where is the longer distance between parallel hoop legs or cross-ties (not more than 300 mm), mm² (core measured to the outside of the hoop, 40 mm cover) and mm².
- A perimeter hoop alone gives mm mm, so cross-ties are provided at every intermediate bar (two across the 450 mm direction and one across the 300 mm direction). The leg spacing is then about mm and mm, so mm. mm²
- One 8 mm leg (50.3 mm²) is not enough, so 10 mm hoops and cross-ties (78.5 mm² 55.6 mm²) are used within , with 135° hooks and a 6φ (≥ 65 mm) extension. With 10 mm hoops, increases by 2 mm and the interaction value becomes about 0.965, still .
- Outside , the spacing must not exceed half the least lateral dimension, mm, so 8 mm ties @ 150 mm c/c are provided.
Detailing
CROSS-SECTION 300 x 450
+-------------------------+
| |
| o o o |
| |
| |
| o o |
| |
| o o |
| |
| |
| o o o |
| |
+-------------------------+
o = 25 mm bars
within l_o (500 mm at each end): 10 mm hoops + cross-ties @ 75 c/c
elsewhere: 8 mm ties @ 150 c/c
Answer: 300 × 450 mm column with 10-25 mm longitudinal bars (); 10 mm hoops with cross-ties @ 75 mm c/c over 500 mm at each end, and 8 mm ties @ 150 mm c/c over the rest of the height.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Column 350x350, 1440 kN, ductile detailing · Design of RCC Structure, chapter 10 · asked 2×
- Short column 300x400, 1400 kN · Design of RCC Structure, chapter 10 · asked 2×
- Short column 350x500, M30, 1500 kN · Design of RCC Structure, chapter 10 · asked 2×
- Ductile detailing of columns, confining steel · Design of RCC Structure, chapter 12 · asked 4×
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Short column 300x500, 2000 kN, M30 · Design of RCC Structure, chapter 10
- Built-up column, battens, 6 m unsupported, 1200 kN · Design of Steel and Timber Structure, chapter 6
- Friction pile length, 300 mm, 250 kN · Foundation Engineering, chapter 8
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Corner stresses of 450 x 750 column (150 kN) · Concrete Technology and Masonry Structure, chapter 8