Short answer

Maximum output 198.8 MW (49.7 MW per unit). Specific speed 74.2, Francis pump-turbine. Safe setting limit 3.2 m above tailwater. Surge: rejection upsurge 9.72 m, downsurge 11.13 m; sudden demand downsurge 13.01 m.

In a pumped-storage hydropower project, water is delivered from the upper impounding reservoir through a low-pressure tunnel and four high-pressure penstocks to the four pump-turbine units. The elevation of the impounding reservoir water level is 500 m, and the elevation of the downstream reservoir water level is 200 m. The maximum reservoir storage which can be utilized continuously for a period of 48 h is 15×10615 \times 10^6 m³. The low pressure tunnel is constructed as follows: length = 4 km; diameter = 8 m; friction factor f = 0.028. The high pressure penstocks (4 nos) are constructed as follows: length of each penstock = 500 m; diameter = 2 m; friction factor f = 0.016; turbine efficiency when generating = 90%; generator efficiency (16 poles, 50 Hz) = 90%; turbine efficiency when pumping = 80%; barometric pressure = 10.3 m of water; Thoma's cavitation coefficient σ=0.043(Ns/100)2\sigma = 0.043 (N_s/100)^2. a) Determine the maximum power output from the installation. b) Estimate the specific speed and specify the type of turbine. c) Determine the safe turbine setting relative to the downstream reservoir water level. d) If a simple surge chamber 6 m in diameter is provided at the end of the low-pressure tunnel, estimate (i) the maximum upsurge and downsurge in the surge chamber for sudden rejection of one unit and (ii) the maximum downsurge for a sudden demand of one unit.

a) Maximum power output

Discharge for 48 h continuous: Q=15×10648×3600=86.81 m3/sQ = \dfrac{15 \times 10^6}{48 \times 3600} = 86.81\ \text{m}^3/\text{s}.

Gross head =500−200=300= 500 - 200 = 300 m.

  • Tunnel: At=π4(8)2=50.27 m2A_t = \frac{\pi}{4}(8)^2 = 50.27\ \text{m}^2, V=1.727V = 1.727 m/s, hft=0.028×4000×1.72722(9.81)(8)=2.13h_{ft} = \dfrac{0.028 \times 4000 \times 1.727^2}{2(9.81)(8)} = 2.13 m
  • Each penstock: q=86.81/4=21.70 m3/sq = 86.81/4 = 21.70\ \text{m}^3/\text{s}, Vp=21.70/3.142=6.908V_p = 21.70/3.142 = 6.908 m/s, hfp=0.016×500×6.90822(9.81)(2)=9.73h_{fp} = \dfrac{0.016 \times 500 \times 6.908^2}{2(9.81)(2)} = 9.73 m
  • Net head Hn=300−2.13−9.73=288.14H_n = 300 - 2.13 - 9.73 = 288.14 m

Turbine power: Pt=ηtγQHn=0.9×9.81×86.81×288.14=220,835P_t = \eta_t\gamma Q H_n = 0.9 \times 9.81 \times 86.81 \times 288.14 = 220{,}835 kW.

Generator output: Pg=0.9×220,835=198,752P_g = 0.9 \times 220{,}835 = 198{,}752 kW.

Maximum power output ≈198.8\approx 198.8 MW (about 49.7 MW per unit).

b) Specific speed and type

Speed from 16 poles at 50 Hz: N=120×5016=375N = \dfrac{120 \times 50}{16} = 375 rpm.

Power per turbine =220,835/4=55,209= 220{,}835/4 = 55{,}209 kW.

Ns=NPHn5/4=37555,209288.141.25=74.2N_s = \frac{N\sqrt{P}}{H_n^{5/4}} = \frac{375\sqrt{55{,}209}}{288.14^{1.25}} = 74.2

This is a low specific speed at high head, so the machine is a Francis-type (reversible pump-turbine).

c) Safe turbine setting

σ=0.043(Ns100)2=0.043(0.742)2=0.0237\sigma = 0.043\left(\frac{N_s}{100}\right)^2 = 0.043(0.742)^2 = 0.0237

Taking Hatm=10.3H_{atm} = 10.3 m (given) and Hv=0.24H_v = 0.24 m (assumed, water at 20 °C):

Hs=Hatm−Hv−σHn=10.3−0.24−0.0237×288.14=3.2 mH_s = H_{atm} - H_v - \sigma H_n = 10.3 - 0.24 - 0.0237 \times 288.14 = 3.2\ \text{m}

The limit is about 3.2 m above the downstream reservoir level. A pump-turbine is normally set well below tailwater (negative HsH_s) because pumping needs more submergence, so this value is only the upper limit.

d) Surge chamber (As=π4(6)2=28.27 m2A_s = \frac{\pi}{4}(6)^2 = 28.27\ \text{m}^2)

The steady friction loss in the tunnel is hf=kV2h_f = k V^2 with k=fL2gDk = \dfrac{fL}{2gD}; the tank level ZZ is measured from the upper reservoir level. Integrating the equations of motion and continuity for the low-pressure tunnel (L=4000L = 4000 m):

  • Four units: Q1=86.81 m3/sQ_1 = 86.81\ \text{m}^3/\text{s}, V=1.727V = 1.727 m/s; three units: Q=65.10 m3/sQ = 65.10\ \text{m}^3/\text{s}, V=1.295V = 1.295 m/s.
  • (i) Rejection of one unit (flow 86.81→65.10 m3/s86.81 \to 65.10\ \text{m}^3/\text{s}): maximum upsurge =9.72= 9.72 m above reservoir level; the following downsurge =11.13= 11.13 m below reservoir level (frictionless amplitude ΔVLAt/gAs=11.6\Delta V\sqrt{LA_t/gA_s} = 11.6 m).
  • (ii) Sudden demand of one unit (flow 65.10→86.81 m3/s65.10 \to 86.81\ \text{m}^3/\text{s}): maximum downsurge =13.01= 13.01 m below reservoir level (about 11.8 m below the initial steady level, which is 1.20 m below reservoir level).

Period of oscillation T=2πLAsgAt=95.2T = 2\pi\sqrt{\dfrac{LA_s}{gA_t}} = 95.2 s.

Answer: (a) 198.8 MW; (b) Ns=74.2N_s = 74.2, Francis (pump-turbine); (c) Hs≈3.2H_s \approx 3.2 m above tailwater (upper limit); (d) upsurge 9.72 m, downsurge 11.13 m (rejection); downsurge 13.01 m (demand).

✓ Answer checked by Claude Opus 5.5 (high effort)

All Hydropower Engineering chapter 7 questions →