Design exceedance Q45% versus Q65%

Short answer

Q45% means rated discharge is the flow equaled or exceeded 45% of the time. Q45% yields higher capacity and more total energy (mainly wet-season) but lower plant factor; Q65% gives smaller, cheaper plant with higher plant factor and lower spill risk. With a firm PPA, sellers usually prefer about Q40–Q45 for higher total revenue.

The design exceedance of hydropower plant Q45%, what does that mean? Compare Q45% with Q65% while designing hydropower plant from the perspective of power producer (seller).

Meaning of Q45%

A design exceedance of Q45% means the plant's design (rated) discharge is the flow that the river equals or exceeds 45% of the time, about 0.45×365≈1640.45 \times 365 \approx 164 days a year. The installed capacity is based on this flow:

P=ηoρg (Q45−Qriparian) HnetP = \eta_o \rho g\,(Q_{45} - Q_{riparian})\,H_{net}

For the other 55% of the time the plant runs at part load, following the river flow. In Nepal, NEA's power purchase practice for ROR projects has moved from about Q65Q_{65} (older practice) to about Q40Q_{40}–Q45Q_{45}.

Comparison from the seller's (IPP) point of view

PointQ45% designQ65% design
Design flowLargerSmaller
Installed capacityHigher (MW)Lower
Annual energyMore (extra wet-season energy)Less
Plant factorLower (about 55–65%)Higher (about 70–80%)
Capital costHigher (bigger waterway, units)Lower
Cost per kWhCan be higher if the extra energy is only wet-seasonLower per kWh
Wet-season spill/curtailment riskHigher (NEA may curtail surplus in monsoon)Lower
Dry-season share of energySmaller proportionLarger proportion
RevenueHigher total, if all energy is boughtLower total, steadier

Seller's view

  • Q45 gives more MW and more total energy, which raises revenue if NEA buys all energy under a take-or-pay PPA. Bank financing and per-MW benefits also favour larger capacity.
  • But most of the extra energy comes in the monsoon, when the tariff is lower (dry-season rate is higher than wet-season rate in NEA's posted rates) and when the grid already has surplus, so spillage or curtailment can reduce income.
  • Q65 gives a smaller, cheaper plant with higher plant factor and lower risk, but loses wet-season energy.
  • The final choice is made by comparing incremental energy and revenue against incremental cost (B/C ratio, IRR) for several exceedance values; with a firm PPA, sellers usually prefer about Q40–Q45.