T/F: impulse withstand and neutral earthing
Short answer
True. Effective earthing reduces temporary overvoltages, allowing a lower-rated arrester and reduced BIL (e.g., 900 kV instead of 1050 kV for 220 kV). Isolated or ungrounded neutral requires full insulation level.
State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: Impulse withstand voltage of an overhead transmission line insulator depends on system (neutral) earthing condition.
TRUE.
- The insulation level (impulse withstand voltage, BIL) is chosen as protection ratio × protective level of the surge arrester.
- The arrester rating depends on the earthing coefficient: with effectively (solidly) earthed neutral the healthy-phase voltage rises to only about 0.8 of line voltage, so an "80% arrester" with a lower protective level is used. With isolated neutral, a "100% arrester" is needed.
- So effective earthing allows a reduced BIL (e.g. 220 kV: 900 kV instead of 1050 kV), and fewer insulator discs; an ungrounded system needs full insulation.
The impulse strength of a given disc does not change, but the required impulse withstand level of the line does depend on neutral earthing.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: earth wire choice depends on circuit and voltage · Transmission and Distribution System Design, chapter 3
- T/F: span choice depends on voltage only · Transmission and Distribution System Design, chapter 4
- T/F: pin insulator cost vs voltage · Transmission and Distribution System Design, chapter 3
- T/F: switching surge ratio vs system voltage · Transmission and Distribution System Design, chapter 3 · asked 4×
- Number of insulator discs for 220 kV line · Transmission and Distribution System Design, chapter 3
- Neutral earthing and insulation level · Transmission and Distribution System Design, chapter 3 · asked 3×
- True/false: load rejection raises terminal voltage · High Voltage Engineering, chapter 3
- True/false: protective ratio and grounding · High Voltage Engineering, chapter 4
- True/false: derivative controllers always used with others · Control Systems, chapter 7 · asked 3×
- True/false: air conditioner is closed loop · Control Systems, chapter 1
All Transmission and Distribution System Design chapter 3 questions →