Transformer inrush current, doubling effect

Short answer

Inrush current is the large transient magnetizing current at energization (5–10 times full-load) due to core saturation. The doubling effect occurs when switching at voltage zero: flux must start from residual flux and can peak at about 2φm + φr, driving the core deep into saturation and demanding high current.

What is meant by transformer inrush current? Discuss the term "doubling effect" in transformer in detail.

Inrush current is the large transient magnetising current drawn by a transformer when it is first connected to the supply. Its peak can reach 5 to 10 times the full-load current (even more in small transformers), and it dies away over a few cycles to a few seconds (longer in large units).

Doubling effect

If the supply voltage is v=Vmsin⁡(ωt+θ)v = V_m\sin(\omega t + \theta), the flux needed in steady state is ϕ=−ϕmcos⁡(ωt+θ)\phi = -\phi_m\cos(\omega t + \theta), because flux lags voltage by 90°. At the instant of switching the flux cannot change suddenly, so it starts from the residual flux ϕr\phi_r, and a decaying transient flux is added to the steady-state value.

Case: switching on at the instant when the supply voltage is zero (ωt=0\omega t = 0).

  • In steady state, the flux at this instant would be at its negative maximum (−ϕm-\phi_m).
  • But the core flux just before switching is the residual flux ϕr\phi_r (often small), and it cannot change suddenly.
  • So the flux starts from ϕr\phi_r and follows
ϕ=ϕr+ϕm(1−cos⁡ωt)\phi = \phi_r + \phi_m(1 - \cos\omega t)
  • Half a cycle later (ωt=π\omega t = \pi), the flux reaches
ϕmax=2ϕm+ϕr\phi_{max} = 2\phi_m + \phi_r

The peak flux is therefore about twice the normal peak, and more if residual flux is present in the same direction. This is the doubling effect.

 flux
  2phi_m |        .-.
         |      /     \
   phi_m |    /   steady-state  
         |  /  .-"-.
      0 -+-/-"------"-------> t
         voltage zero when switched

Consequence

  • A normal transformer is designed to work at a flux density near the knee of the BB–HH curve (about 1.5 to 1.7 T). Twice the flux drives the core deep into saturation, where the permeability falls sharply.
  • A very large magnetising current is then needed to produce this flux, and this is the inrush current. It has a high harmonic content (mainly second harmonic) and decays as the transient flux is damped by the winding resistance.

Case: switching on at voltage maximum gives no transient: the flux starts at zero, which is already its steady-state value at that instant, so the inrush is minimal.

Effects and remedies: inrush can trip overcurrent relays and stress the windings. It is reduced by switching through a series (pre-insertion) resistor and by point-on-wave closing, and relay maloperation is avoided by harmonic restraint in differential relays.