Transformer inrush current, doubling effect
Short answer
Inrush current is the large transient magnetizing current at energization (5–10 times full-load) due to core saturation. The doubling effect occurs when switching at voltage zero: flux must start from residual flux and can peak at about 2φm + φr, driving the core deep into saturation and demanding high current.
What is meant by transformer inrush current? Discuss the term "doubling effect" in transformer in detail.
Inrush current is the large transient magnetising current drawn by a transformer when it is first connected to the supply. Its peak can reach 5 to 10 times the full-load current (even more in small transformers), and it dies away over a few cycles to a few seconds (longer in large units).
Doubling effect
If the supply voltage is , the flux needed in steady state is , because flux lags voltage by 90°. At the instant of switching the flux cannot change suddenly, so it starts from the residual flux , and a decaying transient flux is added to the steady-state value.
Case: switching on at the instant when the supply voltage is zero ().
- In steady state, the flux at this instant would be at its negative maximum ().
- But the core flux just before switching is the residual flux (often small), and it cannot change suddenly.
- So the flux starts from and follows
- Half a cycle later (), the flux reaches
The peak flux is therefore about twice the normal peak, and more if residual flux is present in the same direction. This is the doubling effect.
flux
2phi_m | .-.
| / \
phi_m | / steady-state
| / .-"-.
0 -+-/-"------"-------> t
voltage zero when switched
Consequence
- A normal transformer is designed to work at a flux density near the knee of the – curve (about 1.5 to 1.7 T). Twice the flux drives the core deep into saturation, where the permeability falls sharply.
- A very large magnetising current is then needed to produce this flux, and this is the inrush current. It has a high harmonic content (mainly second harmonic) and decays as the transient flux is damped by the winding resistance.
Case: switching on at voltage maximum gives no transient: the flux starts at zero, which is already its steady-state value at that instant, so the inrush is minimal.
Effects and remedies: inrush can trip overcurrent relays and stress the windings. It is reduced by switching through a series (pre-insertion) resistor and by point-on-wave closing, and relay maloperation is avoided by harmonic restraint in differential relays.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- No load current of single phase transformer · Electric Machine Design, chapter 3
- Bias current effect; closed-loop output impedance · Advanced Electronics, chapter 2
- Positive/negative bias current effect and reduction · Advanced Electronics, chapter 2
- Skin effect with AC and DC current · Power System Analysis I, chapter 4