Line model classification and short-line ABCD
Short answer
Models: short line (≤80 km, series impedance only), medium line (80–250 km, nominal-π or T), long line (>250 km, distributed parameters). Short-line ABCD: A=1, B=Z=R+jX, C=0, D=1. For lagging load, V_S leads V_R and is larger. For leading load, V_S can be less than V_R giving negative regulation.
Classify transmission line models. Find the A, B, C, D parameters of a short transmission line and also draw its phasor diagram with lagging and leading power factor of the load.
Classification of transmission line models
Based on length (for 50 Hz lines):
| Type | Length | Model | Capacitance |
|---|---|---|---|
| Short line | up to about 80 km | Series only | Neglected |
| Medium line | 80–250 km | Nominal-Π or nominal-T | Lumped |
| Long line | above 250 km | Distributed (exact) / equivalent Π or T | Distributed |
ABCD parameters of a short line
The shunt capacitance is neglected, so the same current flows through the whole line.
IS = IR R jX IR
o---->----[ R ]----[ jX ]---->----o
VS VR
o---------------------------------o
Comparing with and :
Check: .
Phasor diagrams
Take as reference. The drop is parallel to and leads by 90°. is the angle between and .
Lagging p.f. load ( lags by ):
+ tip of VS
VS . |
. | IR.X (90 deg
. | ahead of IR)
. d |
O------------------------> VR
\ phiR \ IR.R (along IR)
\ +
v IR
Here and , so regulation is positive and large.
Leading p.f. load ( leads by ):
^ IR
/ IR.X + tip of VS
/ (90 deg \
/ ahead of IR) \
/ VS . + IR.R
/ phiR . / (along IR)
/ . d /
O------------------------> VR
Here ; the drop tilts backwards, so can be less than (negative regulation).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Model validity and nominal-π ABCD with phasor · Power System Analysis I, chapter 5
- Nominal-T phasor diagram and ABCD parameters · Power System Analysis I, chapter 5 · asked 2×
- Nominal-π derivation, losses and UPF phasor diagram · Power System Analysis I, chapter 5
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- Nominal-π model ABCD derivation · Power System Analysis I, chapter 5
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- Loaded transformer and phasor diagram for inductive load · Electrical Machines I, chapter 2
- Synchronous motor features and lagging/leading operation · Electric Machines II, chapter 2
- Reactive power and power phasor diagram · Basic Electrical Engineering, chapter 7