Consequences of computing S = V*I

Short answer

Using S = V*I leaves real power unchanged but reverses the sign of reactive power, making inductive loads appear to supply vars. This contradicts the standard convention where inductive loads absorb positive Q, causing confusion in load flow and compensation studies.

What will be the consequences if AC complex power is calculated as S = V*I? Explain with necessary phasor diagrams.

The standard definition of complex power is S=VI∗=P+jQS = VI^* = P + jQ. With this convention, a lagging (inductive) load absorbs positive QQ. Using S=V∗IS = V^*I gives the same PP but reverses the sign of QQ.

Derivation

Let V=∣V∣∠θvV = |V|\angle\theta_v and I=∣I∣∠θiI = |I|\angle\theta_i, with ϕ=θv−θi\phi = \theta_v - \theta_i (positive for a lagging current).

VI∗=∣V∣∣I∣∠(θv−θi)=∣V∣∣I∣cos⁡ϕ+j∣V∣∣I∣sin⁡ϕV∗I=∣V∣∣I∣∠(θi−θv)=∣V∣∣I∣cos⁡ϕ−j∣V∣∣I∣sin⁡ϕ\begin{aligned} VI^* &= |V||I|\angle(\theta_v-\theta_i) = |V||I|\cos\phi + j|V||I|\sin\phi\\ V^*I &= |V||I|\angle(\theta_i-\theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi \end{aligned}

So V∗I=(VI∗)∗=P−jQV^*I = (VI^*)^* = P - jQ.

Phasor diagrams (inductive load, current lags)

 S = V I*                 S = V* I
      Q>0  S                 V
     ^    /                 /
     |   / phi             / phi  (V ref)
     |  /                 /------> P
     | /                   \
     |/-------> P           \  S
                             v  Q<0
 Inductive load:           Inductive load:
 Q positive (absorbs)      Q appears negative

Consequences of using S=V∗IS = V^*I

  • The real power PP is unchanged, since cos⁡ϕ\cos\phi is even.
  • The sign of QQ is reversed: an inductor (lagging current) would appear to supply reactive power, and a capacitor to absorb it.
  • This contradicts the standard convention (IEEE/IEC) that inductive loads absorb VAr. Generator, motor and load data would be read wrongly.
  • The power factor angle and the power triangle are flipped, so lagging and leading would be confused.
  • In load flow and compensation studies, capacitor banks would be sized in the wrong direction.

Example: Take V=100∠0∘V = 100\angle0^\circ V and I=10∠−30∘I = 10\angle-30^\circ A (inductive load).

  • VI∗=1000∠30∘=866+j500VI^* = 1000\angle30^\circ = 866 + j500: the load absorbs 500 var, which is correct.
  • V∗I=1000∠−30∘=866−j500V^*I = 1000\angle-30^\circ = 866 - j500: this wrongly shows the inductive load as a source of 500 var.

S=VI∗S = VI^* is used so that inductive Q is positive.

✓ Answer checked by Claude Opus 5.5 (high effort)