Consequences of computing S = V*I
Short answer
Using S = V*I leaves real power unchanged but reverses the sign of reactive power, making inductive loads appear to supply vars. This contradicts the standard convention where inductive loads absorb positive Q, causing confusion in load flow and compensation studies.
What will be the consequences if AC complex power is calculated as S = V*I? Explain with necessary phasor diagrams.
The standard definition of complex power is . With this convention, a lagging (inductive) load absorbs positive . Using gives the same but reverses the sign of .
Derivation
Let and , with (positive for a lagging current).
So .
Phasor diagrams (inductive load, current lags)
S = V I* S = V* I
Q>0 S V
^ / /
| / phi / phi (V ref)
| / /------> P
| / \
|/-------> P \ S
v Q<0
Inductive load: Inductive load:
Q positive (absorbs) Q appears negative
Consequences of using
- The real power is unchanged, since is even.
- The sign of is reversed: an inductor (lagging current) would appear to supply reactive power, and a capacitor to absorb it.
- This contradicts the standard convention (IEEE/IEC) that inductive loads absorb VAr. Generator, motor and load data would be read wrongly.
- The power factor angle and the power triangle are flipped, so lagging and leading would be confused.
- In load flow and compensation studies, capacitor banks would be sized in the wrong direction.
Example: Take V and A (inductive load).
- : the load absorbs 500 var, which is correct.
- : this wrongly shows the inductive load as a source of 500 var.
is used so that inductive Q is positive.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Derivation and phasor diagram of complex power · Power System Analysis I, chapter 3
- Generator and load complex power conventions · Power System Analysis I, chapter 3
- Complex power and its significance · Power System Analysis I, chapter 3 · asked 2×
- Complex power and sign conventions · Power System Analysis I, chapter 3
- Complex power and why VI* rather than V*I · Power System Analysis I, chapter 3
- Complex power, impedance and power triangles · Power System Analysis I, chapter 3
- DT complex exponential periodic if rational · Signals and Systems, chapter 1
- Limiting error in calculated power · Instrumentation and Measurement, chapter 1
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2
- Transformer on load and no load, phasor diagrams · Electrical Machines, chapter 2