Power versus distribution transformer

Short answer

Power transformers have high ratings, run near full load, maximize efficiency at full load, allow higher iron loss, use forced cooling. Distribution transformers have lower ratings, are energized continuously, maximize all‑day efficiency near 50–70% load, keep iron loss low, and use natural cooling with low reactance for better regulation.

What are the differences between power transformer and distribution transformer from design aspect?

A power transformer is used in generating stations and transmission substations to step voltages up or down at high power, and runs near full load most of the time. A distribution transformer feeds consumers at the final voltage (for example 11 kV/400 V) and its load varies widely through the day.

Design aspectPower transformerDistribution transformer
Rating and voltageLarge kVA (above ~500 kVA), high voltageSmall kVA (up to ~500 kVA), 11 or 33 kV/400 V
Loading patternNearly full load, switched in/out with loadVaries; energised 24 h even at light load
Max efficiencyDesigned for max efficiency near full loadDesigned for max efficiency at about 50–70% load
Iron vs copper lossIron loss can be higher, copper loss low at full loadIron loss kept low (low BmB_m, good steel); higher copper loss allowed
Efficiency criterionOrdinary (power) efficiencyAll-day (energy) efficiency
EtE_t constant KK (3-ph core)0.6–0.7about 0.45
RegulationNot critical (tap changers used); higher reactance allowed to limit fault currentLow leakage reactance for good regulation
CoolingForced oil/air (ONAF, OFAF)Natural oil cooling (ONAN)

So a distribution transformer is designed with smaller iron loss and better regulation, while a power transformer is designed for high full-load efficiency and to withstand large fault levels.