Motor adjustment to load and excitation effects
Short answer
When load increases, rotor angle δ grows while speed stays synchronous, increasing armature current to match load; beyond δ=90° it pulls out. Changing excitation at constant load varies armature current and pf: under-excited gives lagging pf, normal gives minimum current unity pf, over-excited gives leading pf (synchronous condenser).
Explain how synchronous motor adjust itself for the change in load. Elaborate the effects of change in excitation of synchronous motor on armature current and power factor with proper diagram.
A synchronous motor always runs at synchronous speed . When the shaft load changes it cannot slow down (as an induction motor does); instead the rotor shifts backwards in space by a larger load angle , and the armature current changes to supply the new power.
Adjustment to change in load
- At no load the rotor poles are almost in line with the stator field (), and the motor draws only enough current to meet losses.
- When load torque increases, the rotor momentarily slows down. The rotor poles fall back with respect to the rotating stator field, so increases.
- Back emf stays the same in magnitude (excitation unchanged) but moves further behind . The resultant voltage grows, so armature current increases.
- Power drawn rises until it equals the new load plus losses. The rotor then runs again at with a larger fixed .
- If load exceeds (at for a cylindrical rotor), the motor pulls out of step and stops.
V (fixed)
------------------>
\ delta1
\--------> Ef (light load)
\
\ delta2 > delta1
\------> Ef (heavy load, same length)
Effect of change in excitation (constant load)
With load (and hence ) constant, is constant, so the tip of moves on a line perpendicular to , and is also constant.
| Excitation | vs | Armature current | Power factor |
|---|---|---|---|
| Under-excited | Large | Lagging | |
| Normal | Minimum | Unity | |
| Over-excited | Large | Leading |
I(lead) I(unity)
\ |
\ |
------------ +-------+--------> V
\ |
I(lag) locus of I tip
(I cos(phi) const)
- Raising the field current from a low value first reduces (lagging pf improves) until is minimum at unity pf.
- Further increase makes rise again with a leading pf.
- Plotting against field current gives the V-curves; the pf vs field current curve is an inverted V.
This is why an over-excited synchronous motor can act as a synchronous condenser to improve plant power factor.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Synchronous motor features, applications and excitation · Electric Machines II, chapter 2
- Effect of excitation on armature current and pf · Electric Machines II, chapter 2 · asked 3×
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Current, pf, power and efficiency of 3.3 kV motor · Electric Machines II, chapter 2
- Synchronous motor adjusting to increasing load · Electric Machines II, chapter 2
- Excitation emf and maximum power of 1.5 MW motor · Electric Machines II, chapter 2
- IM and sync motor current adjust with load · Electrical Machine, chapter 5
- Effect of excitation on synchronous motor · Electrical Machine, chapter 6 · asked 6×
- Effect of excitation on synchronous motor · Electrical Machines, chapter 6 · asked 5×
- Armature-controlled DC motor transfer function and block diagram · Control Systems, chapter 2