G-S load flow, j0.12 lines, losses
Short answer
Using G-S with Ybus elements j8.3333 pu (off-diagonal) and −j16.6667 (diagonal), two iterations gave V2 = 0.9576∠−8.87° pu and V3 = 0.9443∠−8.78° pu. Slack bus power: P1 = 2.432 pu, Q1 = 1.005 pu. Since line resistance is zero, real power loss = 0 pu; reactive power loss = 0.418 pu (not fully converged after two iterations).
For a network given below, series impedance of each line is 0 + j0.12 p.u. Shunt admittance of the line is negligible. Calculate: (i) Voltage at bus-2 and bus-3 by using G-S method (upto 2 iteration). (ii) Slack bus real and reactive power. (iii) Network real and reactive power losses. [Figure: three buses with lines 1-2, 1-3 and 2-3; bus 1 is the slack bus with generator, V1 = 1.0∠0°; load at bus 2 = 1.5 + j0.4 p.u; load at bus 3 = 1.2 + j0.5 p.u]
Data and Ybus
Each line: , pu. Every bus has two lines:
Bus 1: slack, . Buses 2 and 3 are PQ buses with net injections and pu. Flat start: .
G-S equation (latest values used immediately):
(i) Iteration 1
Iteration 2
Here and .
| Iteration | (pu) | (pu) |
|---|---|---|
| 0 | ||
| 1 | ||
| 2 |
(ii) Slack bus power (with iteration-2 voltages)
So pu and pu.
(iii) Network losses
Line flows :
| Line | (pu) | (pu) | Loss |
|---|---|---|---|
| 1-2 | |||
| 1-3 | |||
| 2-3 |
Answer:
- pu, pu after 2 iterations.
- Slack bus: pu, pu.
- Losses: real power loss (lines have no resistance); reactive power loss pu.
Note: after only two iterations the solution has not fully converged, so minus the loads () does not yet equal the losses; with more iterations tends to 2.7 pu.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- G-S first iteration with line charging · Power System Analysis II, chapter 2
- N-R first iteration, line reactance 0.1 · Power System Analysis II, chapter 2
- Network losses from given bus voltages · Power System Analysis II, chapter 2
- Ybus for 3-bus lines with shunt susceptance · Power System Analysis II, chapter 1
- G-S load flow with given Ybus, losses · Power System Analysis II, chapter 2
- G-S voltages after 2nd iteration with shunt · Power System Analysis II, chapter 2
- Double-stub shunt tuner for admittance load · RF and Microwave Engineering, chapter 2
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Series R, X and shunt admittance from ABCD · Power System Analysis I, chapter 5
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6