Effects of short circuit faults

Short answer

Short circuits produce excessive current causing thermal damage, mechanical stress, voltage dips, loss of stability, arcing, and supply interruption. Fault calculations are needed to determine breaker ratings, set protective relays, check equipment withstand, design reactors, and perform stability studies.

Describe the effects of short circuit faults on power system. Also, explain the importance of fault calculations.

A short circuit fault is an abnormal low-impedance connection between phases or between phase and earth, which makes very large currents flow.

Effects of short circuit faults

  • Heavy current: fault current may be 5 to 20 times full-load current; I2RI^2R heating can damage windings, cables and insulation.
  • Mechanical forces: electromagnetic force is proportional to I2I^2, so bus bars, transformer and generator windings can be bent or broken.
  • Voltage dip: voltage near the fault falls sharply, so motors may stall and sensitive loads trip.
  • Loss of stability: electrical output of generators falls while mechanical input stays the same, so machines may lose synchronism.
  • Fire and arcing: arcs at the fault can cause fire and explosion, and put people in danger.
  • Unbalance: unsymmetrical faults produce negative sequence currents that overheat the rotors of machines.
  • Interruption of supply to consumers when the faulty section is disconnected.

Importance of fault calculations

  1. Circuit breaker selection: the breaking capacity (MVA, kA) and making capacity of breakers and fuses are chosen from the maximum fault level.
  2. Relay setting and coordination: the minimum and maximum fault currents are needed to set protective relays so they operate selectively.
  3. Equipment rating: bus bars, CTs, cables and switchgear must withstand the thermal and mechanical stress of the fault current.
  4. Design of reactors and grounding: to size current-limiting reactors and neutral grounding impedance that limit the fault level.
  5. Stability studies: fault conditions are used to check transient stability and critical clearing time.
  6. Planning: to check how new generators or interconnections change the fault level of existing substations.