- 2081 Bhadra · 3+5 marks
Stability types; EAC for parallel lines
Short answer
Power system stability is regaining equilibrium. Steady-state: small gradual changes; dynamic: control effects; transient: large disturbance, first swing; voltage stability: bus voltages. Equal area criterion for parallel lines: with one line faulted and cleared, compare accelerating area (Pm - Pe2) from δ0 to δc with decelerating area (Pe3 - Pm) to δmax; stability if A1 ≤ A2. Parallel lines ensure post-fault transfer capability.
State and explain in brief: power system stability, steady state stability, dynamic stability, transient stability and voltage stability. Also, explain in detail how you can use equal area criterion for stability studies in the parallel transmission lines.
Definitions
- Power system stability: the ability of a power system to stay in a state of operating equilibrium under normal conditions and to regain an acceptable equilibrium after a disturbance, with all synchronous machines remaining in synchronism.
- Steady state stability: ability to remain in synchronism for small, gradual changes in load; limit at , with stable operation where .
- Dynamic stability: ability to remain stable for small disturbances over a longer time (several seconds to minutes) when the effects of control systems (AVR, governor, PSS) are included; it concerns damping of low-frequency oscillations.
- Transient stability: ability to remain in synchronism after a large, sudden disturbance (fault, loss of a line, loss of a generator); judged over the first swing (about 1 s).
- Voltage stability: ability of the system to maintain acceptable voltages at all buses after a disturbance; it is lost when reactive power demand cannot be met, leading to voltage collapse.
Equal area criterion for parallel lines
System: generator (, ) feeding an infinite bus () through two parallel lines of reactance each. A 3-phase fault occurs on one line and is cleared by opening the breakers at both ends of that line.
+---[CB]--- X_L ---[CB]---+
E--Xd'--(1) (2)--- V (inf. bus)
+---[CB]--- X_L -x-[CB]---+
F
Three power-angle curves:
with .
Procedure:
- Initial angle: .
- During the fault, ; the rotor accelerates from to the clearing angle . Accelerating area:
- After clearing, the operating point jumps to the post-fault curve; , the rotor decelerates. Decelerating area:
- The system is stable if is reached at some .
- Setting with gives the critical clearing angle:
Pe
^ Pmax1 sin d (pre-fault)
| .-''-.
| .' .--. '. Pmax3 sin d
| / .' A2 '. \ (post-fault)
Pm-------+-+-------+--\------
| /|A1| \ \
| / |..|..... \ \ Pmax2 sin d
+----+--+--+--------+--+--> d
0 d0 dc dmax 180
A1: accelerating area, A2: decelerating area
Having two parallel lines is itself a stability aid: after one line trips, the other still carries power (), so a decelerating area exists.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Equal area criterion for transient stability · Power System Analysis II, chapter 6 · asked 4×
- Steady state vs transient stability; enhancement · Power System Analysis II, chapter 6 · asked 2×
- Voltage stability; transient study assumptions · Power System Analysis II, chapter 6
- EAC for a two machine system · Power System Analysis II, chapter 6
- Types of stability and factors affecting transient · Power System Analysis II, chapter 6
- EAC from given power-angle curves · Power System Analysis II, chapter 6
- Steady state and transient behaviour with governor · Power Plant Equipment, chapter 2 · asked 2×
- T/F: stability criterion implies thermal criterion · Transmission and Distribution System Design, chapter 4 · asked 2×
- When HVDC is economical; equal transmission capacity · Power Electronics, chapter 7
- Equivalent ABCD of lines in parallel · Power System Analysis I, chapter 5