EAC from given power-angle curves

Short answer

The system is stable if cleared before the critical clearing angle. Using equal area criterion, δcr = 55.35°.

A generator is operating at rated voltage and is connected to infinite bus at 50 Hz with power transfer of 1.0 pu. A three-phase fault occurs and it is cleared after some time. Power angle (Pe-δ) curves for the pre-fault condition, during fault and after the fault is cleared is shown in figure below. Use equal area criterion to check whether the system is stable or not. If the system is stable, determine critical clearing angle. [Figure: Pe-δ curves: Curve-I (pre-fault) with peak 1.8 pu; Curve-III (post-fault) with peak 1.3 pu; Curve-II (during fault) with peak 0.4 pu; Pm = 1.0 pu]

Data from the curves: Pm=1.0P_m = 1.0 pu, pre-fault Pmax1=1.8P_{max1} = 1.8 pu, during fault Pmax2=0.4P_{max2} = 0.4 pu, post-fault Pmax3=1.3P_{max3} = 1.3 pu.

Step 1: Can the system be stable?

δ0=sin⁡−11.01.8=33.75∘=0.5890 radδmax=180∘−sin⁡−11.01.3=180∘−50.28∘=129.72∘=2.2640 rad\begin{aligned} \delta_0 &= \sin^{-1}\frac{1.0}{1.8} = 33.75^\circ = 0.5890\ \text{rad} \\ \delta_{max} &= 180^\circ - \sin^{-1}\frac{1.0}{1.3} = 180^\circ - 50.28^\circ = 129.72^\circ = 2.2640\ \text{rad} \end{aligned}

During the fault, Pmax2=0.4<PmP_{max2} = 0.4 < P_m, so the rotor accelerates. After clearing, Pmax3=1.3>PmP_{max3} = 1.3 > P_m, so a decelerating area exists. The system is stable if the fault is cleared before the critical clearing angle, where A1=A2A_1 = A_2.

Step 2: Critical clearing angle

Equating the accelerating area A1A_1 (on curve II, from δ0\delta_0 to δcr\delta_{cr}) with the decelerating area A2A_2 (on curve III, from δcr\delta_{cr} to δmax\delta_{max}):

cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmax−Pmax2cos⁡δ0Pmax3−Pmax2\cos\delta_{cr} = \frac{P_m(\delta_{max}-\delta_0) + P_{max3}\cos\delta_{max} - P_{max2}\cos\delta_0}{P_{max3}-P_{max2}} cos⁡δcr=1.0(2.2640−0.5890)+1.3cos⁡129.72∘−0.4cos⁡33.75∘1.3−0.4=1.6750−0.8307−0.33260.9=0.5685δcr=55.35∘\begin{aligned} \cos\delta_{cr} &= \frac{1.0(2.2640-0.5890) + 1.3\cos129.72^\circ - 0.4\cos33.75^\circ}{1.3-0.4} \\ &= \frac{1.6750 - 0.8307 - 0.3326}{0.9} \\ &= 0.5685 \\ \delta_{cr} &= 55.35^\circ \end{aligned}
 Pe
 1.8 |      ____ I
 1.3 |    /  __ \__ III
 1.0 |---*--|----\---\---- Pm
 0.4 |  / A1| A2  \   \ II
     +--d0--dcr---dmax---- delta
       33.75 55.35 129.72

Answer: The system is stable if the fault is cleared at an angle below the critical clearing angle δcr≈55.35∘\delta_{cr} \approx 55.35^\circ; if clearing is later, it loses synchronism.