Zbus vs Ybus; off-nominal transformer model
Short answer
Ybus is sparse, formed by inspection, used for load flow; Zbus is full, built algorithmically, used for fault analysis. For an off-nominal transformer 1:t with leakage admittance y, Ybus = [[t²y, –ty],[–ty, y]]. The π-model has series ty, shunt t(t‑1)y on the tap side, and (1–t)y on the other side.
What are difference between bus impedance matrix (Zbus) and bus admittance matrix (Ybus)? Develop Ybus for regulating transformers whose off-nominal turn ratio is 1:t and draw the equivalent π-model for this transformer.
Zbus versus Ybus
| Point | ||
|---|---|---|
| Relation | ||
| Structure | Sparse | Full (dense) |
| Formation | By inspection, simple | Building algorithm or inversion |
| Elements | Driving-point and transfer admittances | Driving-point and transfer impedances |
| Main use | Load flow (G-S, N-R) | Short-circuit (fault) studies |
| Modification | Easy | Needs building steps |
Ybus for a regulating (off-nominal tap) transformer
Model the transformer as an ideal transformer of ratio in series with its per-unit leakage admittance placed on the tap (bus q) side. Bus p is on the "1" side, bus q on the "t" side.
p Ip 1 : t x y Iq q
o----->----)|(------o--[===]----<-----o
Vp Vx = t Vp
Ideal transformer: . Let be the current leaving node x towards q, so . Being lossless, , which with real gives :
In matrix form:
So the transformer adds to , to and to , .
Equivalent π-model
Match a π circuit (series , shunts at p and at q) to the matrix: , , :
p t*y q
o--------[=====]----------o
| |
[ t(t-1)y ] [ (1-t)y ]
| |
=== ===
If , the shunts vanish and the model becomes the simple series admittance . For the two shunt branches have opposite signs (one acts inductive, the other capacitive), which is how the tap changes reactive power flow and bus voltage.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Ybus derivation for 3-bus π-model network · Power System Analysis II, chapter 1 · asked 2×
- Ybus, Zbus and 4-bus Ybus formulation · Power System Analysis II, chapter 1
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×
- Bus admittance matrix and its elements · Power System Analysis II, chapter 1
- Ybus modified by phase-shifting transformer · Power System Analysis II, chapter 1
- Node equations and Ybus, six-bus network · Power System Analysis II, chapter 1
- Equivalent impedance and copper loss of 50 kVA transformer · Electrical Machines I, chapter 2
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×