- 2070 Bhadra · 8 marks
Minimum sewer diameter, 80000 population
Short answer
Peak sewage Q=0.3222 m³/s, d/D=0.75 gives Q/Q_f=0.9119, so Q_f=0.3534 m³/s. From Manning's with n=0.013, S=1/400, D=0.632 m; provide 675 mm. Velocity at d/D=0.75 is 1.33 m/s, well within permissible limits.
The population of a town is 80,000 persons with a water supply rate of 145 lpcd. Assuming 80% of water supply contributes for sewage flow, taking Manning's N as 0.013, average slope as 1:400 and peak factor as 3, determine the minimum diameter of sewer required to carry the maximum discharge if it runs at 0.75 depths?
Design flow
Data: , (constant), depth ratio .
For : , , , so and (n taken constant).
Size of the sewer
Discharge when running full:
Manning's formula for a full circular pipe, , with and :
Adopt the next standard size, D = 675 mm.
Check of velocity and capacity
For the adopted pipe: m/s and m³/s.
The velocity at maximum flow, 1.33 m/s, lies between the minimum (0.6 m/s) and the maximum non-scouring limit (3.0 m/s), so it is satisfactory.
Answer: Minimum diameter required = 0.632 m; provide 675 mm.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sewer diameter for a 2.5 sq km area · Sanitary Engineering, chapter 3
- Separate sewer, 0.6 full, 250000 persons · Sanitary Engineering, chapter 3 · asked 2×
- Sewer diameter for a 12 sq km area · Sanitary Engineering, chapter 3
- Separate sewer, 0.70 full, 100000 persons · Sanitary Engineering, chapter 3 · asked 2×
- Circular sedimentation tank, population 80000 · Sanitary Engineering, chapter 7 · asked 2×
- Oxidation pond for Terai town, 12,000 · Sanitary Engineering, chapter 7
- Service reservoir of 30 m diameter, 1,00,000 population · Water Supply Engineering, chapter 7
- Number and size of RSF, 1,20,000 population · Water Supply Engineering, chapter 6
- Population 2090 by three methods, 110 lpcd · Water Supply Engineering, chapter 3 · asked 2×
- Design pipes AB and BC, 20,000 population, f = 0.04 · Water Supply Engineering, chapter 7