Footing for 400x400 column, 1500 kN
Short answer
Provide a 3.4 m x 3.4 m square footing, overall depth 650 mm (d=590 mm). Reinforcement: 16 mm bars @185 mm c/c both ways. One-way shear and punching shear are within limits; bearing stress check requires dowels, satisfied by continuing the column’s 8–20 mm bars.
Design a footing for supporting a square column of 400 mm x 400 mm. The column carries a service load of 1500 kN. The safe bearing capacity of soil is 150 kN/m. Use M20 concrete and Fe415 grade steel.
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Column bars not given; 8-20 mm assumed. Loads are service loads.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 11.56 m² 11.00 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 744.5 | 3633 | 16 mm @ 185 c/c | 3695 |
| Along (width ) | 744.5 | 3633 | 16 mm @ 185 c/c | 3695 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1450 mm along , 1450 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 810 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 32 = 568 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN (3.4 m x 3.4 m)
+------------------------------------+
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | +----------+ | | | |
|--+---+---+-| column |--+---+---+-|
| | | | +----------+ | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
+------------------------------------+
| = bars along B, - = bars along L: 16 mm @ 185 c/c both ways
ELEVATION
| column |
| |
+---------------+----------+---------------+
| (dowels) | D = 650 mm
| o o o o o o o o o o o o o | bottom mesh, 50 mm cover
+------------------------------------------+
<---------------- 3400 mm ----------------->
- Bottom mesh: 16 mm @ 185 c/c along (lower layer), 16 mm @ 185 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.4 m × 3.4 m × 650 mm thick; 16 mm @ 185 c/c along the length and 16 mm @ 185 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 1250 kN column load, depth 1.8 m · Design of RCC Structure, chapter 11
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 350x350, 1500 kN · Design of RCC Structure, chapter 11
- Soil exploration, safe bearing capacity, improvement · Building Technology, chapter 2
- Allowable load of 400 mm pile, layered soil · Foundation Engineering, chapter 8
- Safe load P on bolted bracket, M20 4.6 · Design of Steel and Timber Structure, chapter 4
- RCC column with footing: concrete and steel · Estimating and Costing, chapter 6