Rectangular footing, 600x600 column, 1150 kN
Short answer
Footing size 4.0 m × 2.2 m, 850 mm deep. Longitudinal steel 16 mm @ 155 mm c/c; transverse steel central band 16 mm @ 145 mm c/c and outer strips 16 mm @ 175 mm c/c.
Design a rectangle footing to carry a column load of 1150 kN and BM of 250 kN-m from 600 x 600 mm square column with the 20 mm diameter steel. The bearing capacity of soil is 200 kN/m. Consider depth of foundation as 1.5 m. Take unit weight of earth is 17 kN/m. Use M20 concrete and Fe 415 steel.
Data and assumptions
- Column 600 mm × 600 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 200 kN/m² at 1.5 m depth, soil unit weight 17 kN/m³.
- Loads are service loads.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Net safe bearing capacity = kN/m² (this takes care of the weight of footing and backfill).
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 196.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 768.8 | 2790 | 16 mm @ 155 c/c | 2854 |
| Along (width ) | 250.9 | 4080 | 16 mm @ 195 c/c | 4124 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 145 mm c/c (15 bars).
- Each outer strip (900 mm wide): remaining steel 592 mm² or minimum 0.12% = 918 mm², whichever is more → 16 mm @ 175 mm c/c (5 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1650 mm along (adequate), 750 mm along . Along the available 750 mm is slightly less than mm, so the bars are given 90° bends at the ends (each bend adds an anchorage value of mm), which is adequate.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 3240 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1800 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 850 - 50 - 32 = 768 mm , adequate.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 850 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.0 m, B = 2.2 m
- Bottom mesh: 16 mm @ 155 c/c along (lower layer); along (upper layer), 16 mm @ 145 c/c in the central 2.2 m band and 16 mm @ 175 c/c in each outer strip, 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 4.0 m × 2.2 m × 850 mm thick; 16 mm @ 155 c/c along the length; along the width, 16 mm @ 145 c/c in the central 2.2 m band and 16 mm @ 175 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Footing, 1250 kN column load, depth 1.8 m · Design of RCC Structure, chapter 11
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 450x500 column, 6#20, uniaxial moment · Design of RCC Structure, chapter 11
- Footing with load transfer check, 1000 kN · Design of RCC Structure, chapter 11
- Footing for 400x400 column, 1500 kN · Design of RCC Structure, chapter 11
- Bolted bracket connection, 200 kN at 250 mm · Design of Steel and Timber Structure, chapter 4
- Square footing under eccentric load, min depth · Foundation Engineering, chapter 6
- Square deodar column 4 m, 250 kN, open shed · Design of Steel and Timber Structure, chapter 11
- Square footing size in clay, 750 kN · Foundation Engineering, chapter 6