Francis diameter and setting (110 m, 140 m³/s)

Short answer

Use 4 units of 34 MW; speed 230.8 rpm, runner diameter about 2.69 m; runner outlet should be at most about 3.3 m above tailrace water level.

Determine the diameter of a Francis turbine for a site where the net head is 110 m and discharge 140 m³/sec having efficiency of 90%. Determine also the elevation of the turbine with reference to the water surface in the tailrace. Assume the turbine will have to drive a 50 cycle generator.

Step 1: Power and units

P=ηγQH=0.90×9.81×140×110=135,967 kWP = \eta\gamma Q H = 0.90 \times 9.81 \times 140 \times 110 = 135{,}967\ \text{kW}

Number of units: adopt 4 units, each Q=35Q = 35 m³/s and Pu=33,992P_u = 33{,}992 kW.

Step 2: Specific speed and rated speed

For Francis turbines (metric units, kW, m, rpm) the empirical relation of Schweiger and Gregory is

Ns=3763H0.854+49.4=117.3N_s = \frac{3763}{H^{0.854}} + 49.4 = 117.3 N=NsH5/4Pu=226.7 rpmN = \frac{N_s H^{5/4}}{\sqrt{P_u}} = 226.7\ \text{rpm}

Synchronous speed at 50 Hz: N=6000/pN = 6000/p. Adopt p=26p = 26 poles, N=230.8N = 230.8 rpm. Actual specific speed:

Ns=NPuH5/4=119.4N_s = \frac{N\sqrt{P_u}}{H^{5/4}} = 119.4

Step 3: Runner diameter

Peripheral speed u=Ku2gHu = K_u\sqrt{2gH} with Ku=0.7K_u = 0.7 (range 0.6 to 0.9):

u=0.72×9.81×110=32.52 m/s,D=60uπN=60×32.52π×230.8=2.69 mu = 0.7\sqrt{2 \times 9.81 \times 110} = 32.52\ \text{m/s}, \qquad D = \frac{60u}{\pi N} = \frac{60 \times 32.52}{\pi \times 230.8} = 2.69\ \text{m}

Step 4: Setting (Thoma cavitation coefficient)

σc=0.0432(Ns100)2=0.0616\sigma_c = 0.0432\left(\frac{N_s}{100}\right)^2 = 0.0616

Sea-level site assumed: Hatm=10.3H_{atm} = 10.3 m, Hv=0.24H_v = 0.24 m.

Hs=Hatm−Hv−σcH=10.3−0.24−0.0616×110=3.28 mH_s = H_{atm} - H_v - \sigma_c H = 10.3 - 0.24 - 0.0616 \times 110 = 3.28\ \text{m}

This is the highest permissible level of the runner outlet above tailwater; in practice set lower (safety margin 1 to 2 m, and reduce HatmH_{atm} by about 1 m per 900 m of site elevation).

Answer: 4 units of 34 MW; N=230.8N = 230.8 rpm (50 Hz, 26 poles); runner diameter D≈2.69D \approx 2.69 m; runner outlet at about 3.3 m above tailrace water level as the upper limit (set lower in practice).