Short answer

Auxiliary systems: governor/oil pressure for speed control, cooling water for generator/bearings, excitation/AVR, station AC/DC supply, diesel generator for black start, protection/SCADA. Ancillary systems: fire fighting, EOT crane, HVAC, earthing, lighting, intake gate control. They ensure safe start, operation and shutdown of the 100 MW Francis turbine unit.

Name the auxiliary and ancillary systems with their function in a hydropower plant with Francis turbine of 100 MW.

Auxiliary systems are the supporting systems that the main generating unit needs to start, run and stop safely. Ancillary systems are plant-wide support systems (station services, safety, handling) that are not part of the energy conversion itself. For a 100 MW plant with Francis turbines (assume 2 × 50 MW or 3 units), they are as follows.

Mechanical auxiliary systems

SystemFunction
Governor and oil pressure unitMoves wicket gates to control speed/load; accumulator stores oil pressure
Main inlet valve (butterfly/spherical) with hydraulic unitIsolates the turbine from the penstock; emergency closure
Cooling water systemCools generator air coolers, bearings, transformer (via heat exchangers); pumps, filters, strainers
Lubrication / bearing oil systemLubricates thrust and guide bearings; high-pressure oil lifting during start
Brake and jacking systemStops the rotor at low speed; lifts the rotor for inspection
Drainage and dewatering systemRemoves leakage water; empties draft tube and spiral case for maintenance
Compressed air systemBrakes, governor accumulator air, tools; depresses draft tube water for synchronous condenser mode
Shaft seal waterPrevents water leakage at the turbine shaft

Electrical auxiliary systems

SystemFunction
Excitation system and AVRField current, voltage and var control
Generator neutral groundingLimits earth-fault current
Station service AC (UAT, station transformer, 415 V boards)Power to all auxiliaries
Emergency diesel generatorBlack start and backup supply
DC system (battery + chargers)Protection, control, emergency loads
Protection, control, SCADA and synchronisingSafe automatic operation
Metering and communication (PLCC, fibre)Energy accounting, dispatch link

Ancillary systems

SystemFunction
Fire detection and fighting (CO2 for generator, water spray for transformer, hydrants)Safety from fire
Heating, ventilation and air conditioningKeeps powerhouse and control room within temperature/humidity limits
EOT crane in powerhouseErection and maintenance of heavy parts
Lighting and emergency lightingNormal and safe operation
Earthing and lightning protectionPersonnel and equipment safety
Water supply and sewerage, oil handling and purificationPlant services
Workshop, stores, CCTV and securityMaintenance and safety
Intake and gate control, desander flushing, trash rack cleaningWater conveyance operation

In addition, the plant provides ancillary services to the grid: frequency regulation, reactive power/voltage support, spinning reserve and black start.

✓ Answer checked by Claude Opus 5.5 (high effort)