- 2075 Baisakh · 4 marks
P and Q of a 100 V single-phase source
Short answer
Complex power S = VI* = 1000∠-10° VA = 984.8 - j173.65 VA. The source delivers 984.8 W real power and absorbs 173.6 var reactive power.
A single phase voltage source with V = 100∠0° volts delivers a current I = 10∠10° A, which leaves the positive terminal of the source. Calculate the source real and reactive power and state whether the source delivers or absorbs each of these.
Complex power delivered by a source whose current leaves its positive terminal is (generator convention). A positive P or Q then means the source delivers it; a negative value means it absorbs it.
- W: positive, so the source delivers real power.
- var: negative, so the source absorbs 173.65 var (equivalently it delivers var).
The current leads the voltage by 10°, so the load connected to the source is capacitive; a capacitive load supplies reactive power, which flows back into the source.
Answer: P = 984.8 W delivered; Q = 173.6 var absorbed by the source.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Line as source and sink of reactive power, effects · Power System Analysis I, chapter 6
- Line as source and sink of reactive power · Power System Analysis I, chapter 6
- Reactive power proportional to voltage drop · Power System Analysis I, chapter 6
- Reactive power flow between machines via j10 Ω · Power System Analysis I, chapter 3
- Source P and Q, Ean = -120∠210° V · Power System Analysis I, chapter 3
- Direction of active and reactive power flow · Power System Analysis I, chapter 6
- Generator reactive power at constant terminal voltage · Power System Analysis II, chapter 1
- Single-phase current source inverter · Power Electronics, chapter 5
- Single-phase current source inverter with AC motor · Power Electronics, chapter 5
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×