- 2071 Shrawan · 6 marks
Line opened: stability and rotor swing
Short answer
The system remains stable. The rotor swings to about 69.9° and then oscillates around the new equilibrium of 48.6°.
The power system shown in figure below is operating in steady state with which the generator delivering 1.5 p.u power to the infinite bus. The circuit breaker A suddenly opens and remain open. Find (i) whether the system remains stable or not. (ii) Angle to which the rotor swings. [Figure: generator E' = 1.2 p.u, X'd = 0.2 p.u; two parallel lines, the upper with X1 = 0.4 p.u and the lower with circuit breakers A and B; infinite bus E = 1.0 p.u]
Data: pu, pu, pu, pu, pu.
Assumption: the lower line's reactance is not marked, so it is taken equal to the upper line ( pu). Opening breaker A disconnects the lower line.
Step 1: Before and after opening
New equilibrium: . Limit: .
Step 2: (i) Stability check
Accelerating area (from to ):
Maximum decelerating area (from to ):
Since , the system remains stable.
Step 3: (ii) Maximum rotor swing
From , the net area from to is zero:
Solving by trial: rad.
Answer: (i) stable; (ii) the rotor swings to about 69.9° and then oscillates about the new equilibrium of 48.6°.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Fault cleared at 45°: stability and maximum swing · Power System Analysis II, chapter 6
- Stability after tripping one circuit · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Stability definitions and swing equation from dynamics · Power System Analysis II, chapter 6
- Mid-line fault, cleared at 60° · Power System Analysis II, chapter 6
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Valve suddenly opened: time to 95% flow · Hydraulics, chapter 4
- Choice of generator circuit breaker · Power Plant Design, chapter 4 · asked 2×
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3