- 2070 Asar · 8 marks
Stability after tripping one circuit
Short answer
The system remains stable. The rotor swings to approximately 69.9° and settles at the new equilibrium angle of 48.6°.
For the system shown in figure below, the numerical values for different quantities are: E = 1.2 pu, V = 1 pu, Xs = 0.2 pu and reactance of each line is 0.4 pu. Initially the generator is delivering a power of 1.5 pu. If one of the double circuit lines is now tripped out, using equal area criteria determine whether the system would be able to maintain its stability or not. [Figure: generator E∠δ - double circuit line, each circuit X = j0.4 p.u with circuit breakers at both ends - infinite bus V∠0°]
Data: pu, pu, pu, each line pu, pu.
Step 1: Power-angle curves
Step 2: Angles
When the line trips, drops to , so the rotor accelerates.
Step 3: Equal areas
Accelerating area, from to :
Maximum decelerating area, from to :
Pe
3.0 | ___ before (3 sin d)
2.0 | / _ \__ after (2 sin d)
1.5 |---/-*-----\----\---- Pm
| /A1| A2 \ \
+-30--48.6--69.9--131.4 delta
Step 4: Result
, so the system is stable and keeps synchronism.
Equating , that is , gives a maximum swing of . The rotor then settles at .
Answer: Stable; the rotor swings to about 69.9° and settles at 48.6°.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Mid-line fault cleared at 60°, E = 1.04 · Power System Analysis II, chapter 6
- Line flows by G-S after one iteration · Power System Analysis II, chapter 2
- N-R one iteration, P2 = 0.4 pu · Power System Analysis II, chapter 2
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- N-R first iteration, line reactance 0.1 · Power System Analysis II, chapter 2
- G-S one iteration with π-model lines · Power System Analysis II, chapter 2
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Capacitance of double circuit line, 9 mm radius · Power System Analysis I, chapter 4