- 2081 Bhadra · 2+3+3 marks
Stored energy and rotor acceleration
Short answer
Stored energy = GH = 800 MJ. Acceleration alpha = 337.5 elec deg/s^2 (28.125 rpm/s). After 10 cycles, rotor angle increases by 6.75 elec deg and speed reaches 1505.625 rpm.
A 50 Hz, 4 pole turbo generator 100 MVA, 11 kV has an inertia constant 8 MJ/MVA. (i) find the stored energy in the rotor at synchronous speed. (ii) If the mechanical input is suddenly raised to 80 MW for an electrical load of 50 MW, find rotor acceleration, neglecting mechanical and electrical losses. (iii) if acceleration calculated in part (ii) is maintained for 10 cycles, find the change in torque and rotor speed in revolutions/minute at end of this period.
Data: MVA, MJ/MVA, Hz, 4 poles. Synchronous speed rpm.
(i) Stored energy at synchronous speed
(ii) Rotor acceleration
Accelerating power: MW.
The inertia constant in MJ·s/elec-degree is
Swing equation: , so
(iii) After 10 cycles
Time: s. Starting from synchronous speed with constant :
The change in torque (load) angle is
The rotor speed at the end of 10 cycles is
"Change in torque" is read here as the change in torque (load) angle, which is the usual form of this problem. For reference, the accelerating torque is N·m.
Answer: (i) 800 MJ; (ii) elec deg/s² (28.125 rpm/s); (iii) elec deg, speed rpm.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Inertia constant on 500 MVA base · Power System Analysis II, chapter 6
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- L-L fault on 40 MVA generator · Power System Analysis II, chapter 5
- L-L fault currents and voltages, 30 MVA generator · Power System Analysis II, chapter 5
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- 440 V IM with 50 kW rotor input · Electrical Machine, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- Speed of 4 and 6 pole alternators for 50 Hz · Electrical Machines, chapter 6