Microprocessor relaying via generator field current
Short answer
A microprocessor-based loss-of-field protection monitors the generator field current via a shunt or Hall sensor. The signal is isolated, filtered, scaled, sampled, and digitized. The microprocessor compares the field current with a set minimum (20–40% of no-load value); if below for a set delay (0.5–2 s), it issues an alarm and trips the generator and field circuit breakers. The scheme includes self-checking, data logging, and can add undervoltage or reactive power confirmation.
Describe with neat block diagram, the microprocessor based relaying scheme for the protection of generator by monitoring the field current of the alternator.
Loss-of-field (field failure) protection of an alternator can be done by a microprocessor that continuously monitors the field (excitation) current. If the field current falls below a set minimum (field open, short-circuited, or AVR/exciter failure), the generator loses synchronism and draws large reactive power from the system; the scheme gives an alarm and trips the generator after a short delay.
Block diagram
Exciter ──► Field winding of alternator
│
[Shunt / Hall-effect current
sensor in field circuit]
│ V ∝ I_f
[Isolation amplifier / filter]
│
[Signal conditioner (0–5 V)]
│
[Sample & hold] ─► [A/D converter]
│
┌─────────────────────────────▼─────┐
│ MICROPROCESSOR │
│ ROM: program RAM: data │
│ Set value I_f(min), time delay │
└──────┬──────────┬───────────┬─────┘
│ │ │
[Output port] [Display] [Clock/timer]
│
[Driver + aux relay]──► Alarm
└──────────────► Trip gen. CB
& field CB
Working
- Sensing: the DC field current I_f is measured by a shunt (or Hall sensor) giving a small voltage proportional to I_f. An isolation amplifier separates the field circuit from the electronics and filters ripple.
- Conversion: the signal is scaled to the ADC range (e.g. 0–5 V), sampled and converted to a digital number.
- Program logic:
- Read the ADC value at regular intervals and convert to field current.
- Compare with the stored minimum value I_f(min) (e.g. 20–40% of no-load field current; set from the generator's capability curve).
- If I_f ≥ I_f(min): healthy, repeat.
- If I_f < I_f(min): start a timer (about 0.5–2 s) to avoid tripping on transient dips or swings.
- If the low value persists for the set time: give alarm, then send trip signal to the generator CB and field CB.
- Output: the output port drives a transistor/auxiliary relay that trips the breakers; the display shows field current and status.
Start → Read I_f → I_f < I_min ? ─No─► loop
│Yes
Start/continue timer
│
t > t_set ? ─No─► loop
│Yes
Alarm + Trip CBs
Advantages: simple, accurate settings, self-checking, and the same microprocessor can also log data and add an under-voltage or reactive-power check to confirm loss of field.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Microprocessor-based transmission line protection · Switchgear and Protection, chapter 8 · asked 2×
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Unit protection scheme · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Combined phase and earth fault protection of generator · Switchgear and Protection, chapter 7
- Percentage differential protection of alternator · Switchgear and Protection, chapter 7 · asked 2×
- DC motor θm/Va via block diagram · Control Systems, chapter 2
- Microprocessor based system and bus organization · Microprocessor, chapter 1 · asked 5×
- Protection for alternator and step-up transformer · Power Plant Design, chapter 4
- Features of microprocessor based instrumentation · Instrumentation II, chapter 1 · asked 4×