Isolated footing 350x500, 2000 kN
Short answer
Rectangular footing 3.9 m × 2.3 m, depth 800 mm (effective 740 mm). Longitudinal steel: 16 mm @ 150 mm c/c; transverse: 16 mm @ 205 mm c/c with central band of 14 bars @ 160 mm c/c per IS 456.
Design the isolated footing of a column of 350 mm x 500 mm. Column is subjected to design axial load of 2000 kN and design BM of 80 kN-m. Allowable bearing capacity of soil is equal to 175 kN/m.
Data and assumptions
- Column 500 mm × 350 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 175 kN/m².
- The question gives design (factored) loads; M20 concrete and Fe415 steel are assumed, with 8-20 mm column bars.
- Moment acts about the minor axis, varying the pressure along the 500 mm side.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 223.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 773.4 | 3006 | 16 mm @ 150 c/c | 3083 |
| Along (width ) | 413.3 | 3744 | 16 mm @ 205 c/c | 3825 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 160 mm c/c (14 bars).
- Each outer strip (800 mm wide): remaining steel 483 mm² or minimum 0.12% = 768 mm², whichever is more → 16 mm @ 200 mm c/c (4 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1650 mm along , 925 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1575 kN kN, so the excess 425 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels, which is adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 800 - 50 - 32 = 718 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 800 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.9 m, B = 2.3 m
- Bottom mesh: 16 mm @ 150 c/c along (lower layer); along (upper layer), 16 mm @ 160 c/c in the central 2.3 m band and 16 mm @ 200 c/c in each outer strip, 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.9 m × 2.3 m × 800 mm thick; 16 mm @ 150 c/c along the length; along the width, 16 mm @ 160 c/c in the central 2.3 m band and 16 mm @ 200 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 350x350, 1500 kN · Design of RCC Structure, chapter 11
- Isolated footing 500x500, 1600 kN · Design of RCC Structure, chapter 11
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing with load transfer check, 1000 kN · Design of RCC Structure, chapter 11
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Box deodar column, 60 mm planks, 350 kN · Design of Steel and Timber Structure, chapter 11
- Allowable load of 400 mm pile, layered soil · Foundation Engineering, chapter 8
- Timber column under axial load and bending · Design of Timber and Masonry Structures, chapter 3