Peaking RoR: max power and wet/dry energy ratio

Short answer

Design flow Q25 is 800 m³/s. Maximum power is 1962 MW for 100% efficiency (1668 MW for 85% efficiency). Wet season to dry season energy ratio is 3.48.

A peaking ROR project in western Nepal with net head of 250 m has the following river flow data:

MonthJanFebMarAprMayJunJulAugSepOctNovDec
River flow (m³/s)100808010520050011001200800350200120

The storage capacity available for this project is 1100 million m³. This storage capacity is utilized for dry months (Nov-May) during which the plant is used as a peak load plant operating 4 hours a day. Considering design flow as Q₂₅, calculate the maximum power generation (in MW) and the ratio of wet season energy to dry season energy.

Data and assumptions

Net head H=250H=250 m. Dry months (Nov-May, 7 months) use stored water for 4 h/day of peaking. Wet months (Jun-Oct, 5 months) the plant runs as RoR for 24 h. One month =730=730 h =2.628×106=2.628\times10^6 s. Overall efficiency is not given, so power is first found for η=1\eta=1 and then for a typical η=0.85\eta=0.85; the energy ratio does not depend on η\eta.

Design flow Q25Q_{25}

Arrange the 12 monthly flows in descending order: 1200, 1100, 800, 500, 350, 200, 200, 120, 105, 100, 80, 80. The flow equalled or exceeded 25% of the time (3 months out of 12) is the 3rd value:

Q25=800 m3/sQ_{25} = 800\ \text{m}^3/\text{s}

Is the stored water enough for peaking at Q25Q_{25}?

  • Dry-season inflow volume =∑Q×2.628×106=885×2.628×106=2,326×106=\sum Q\times 2.628\times10^6 = 885\times2.628\times10^6 = 2,326\times10^6 m³
  • Plus live storage =1100×106=1100\times10^6 m³, so water available =3,426×106=3,426\times10^6 m³
  • Peaking hours in 7 months =7×730×424=851.7=7\times730\times\frac{4}{24} = 851.7 h
  • Water needed to run at Q25Q_{25} for these hours =800×851.7×3600=2,453×106=800\times851.7\times3600 = 2,453\times10^6 m³ (less than available)

So the turbines can run at Q25=800Q_{25}=800 m³/s during the 4 peak hours every day, and the plant capacity is controlled by the design flow (the water available would allow up to 1,117 m³/s).

Maximum power

Pmax=9.81 η Q H=9.81×η×800×250=1,962 η MWP_{max} = 9.81\,\eta\,Q\,H = 9.81\times\eta\times800\times250 = 1,962\,\eta\ \text{MW}
  • With η=1\eta = 1: Pmax=1,962P_{max} = 1,962 MW
  • With η=0.85\eta = 0.85: Pmax=1,668P_{max} = 1,668 MW

Wet-season to dry-season energy ratio

Wet season flows used: min⁡(Q,800)\min(Q,800) = 500, 800, 800, 800, 350, total =3250=3250 m³/s-months.

Ewet∝3250×730=2,372,500,Edry∝800×851.7=681,333E_{wet} \propto 3250\times730 = 2,372,500,\qquad E_{dry} \propto 800\times851.7 = 681,333 EwetEdry=2,372,500681,333=3.48\frac{E_{wet}}{E_{dry}} = \frac{2,372,500}{681,333} = 3.48

Answer: maximum power = 1,962 MW for η=1\eta=1 (1,668 MW for η=0.85\eta=0.85); wet season energy / dry season energy = 3.48.