- 2078 Bhadra · 12 marks
Peaking RoR: max power and wet/dry energy ratio
Short answer
Design flow Q25 is 800 m³/s. Maximum power is 1962 MW for 100% efficiency (1668 MW for 85% efficiency). Wet season to dry season energy ratio is 3.48.
A peaking ROR project in western Nepal with net head of 250 m has the following river flow data:
| Month | Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| River flow (m³/s) | 100 | 80 | 80 | 105 | 200 | 500 | 1100 | 1200 | 800 | 350 | 200 | 120 |
The storage capacity available for this project is 1100 million m³. This storage capacity is utilized for dry months (Nov-May) during which the plant is used as a peak load plant operating 4 hours a day. Considering design flow as Q₂₅, calculate the maximum power generation (in MW) and the ratio of wet season energy to dry season energy.
Data and assumptions
Net head m. Dry months (Nov-May, 7 months) use stored water for 4 h/day of peaking. Wet months (Jun-Oct, 5 months) the plant runs as RoR for 24 h. One month h s. Overall efficiency is not given, so power is first found for and then for a typical ; the energy ratio does not depend on .
Design flow
Arrange the 12 monthly flows in descending order: 1200, 1100, 800, 500, 350, 200, 200, 120, 105, 100, 80, 80. The flow equalled or exceeded 25% of the time (3 months out of 12) is the 3rd value:
Is the stored water enough for peaking at ?
- Dry-season inflow volume m³
- Plus live storage m³, so water available m³
- Peaking hours in 7 months h
- Water needed to run at for these hours m³ (less than available)
So the turbines can run at m³/s during the 4 peak hours every day, and the plant capacity is controlled by the design flow (the water available would allow up to 1,117 m³/s).
Maximum power
- With : MW
- With : MW
Wet-season to dry-season energy ratio
Wet season flows used: = 500, 800, 800, 800, 350, total m³/s-months.
Answer: maximum power = 1,962 MW for (1,668 MW for ); wet season energy / dry season energy = 3.48.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- RoR capacity, peaking capacity and benefit · Hydropower Engineering, chapter 3
- Installed capacity, energy and daily peaking reservoir (2079) · Hydropower Engineering, chapter 3 · asked 2×
- Installed capacity, energy and daily peaking reservoir (2072) · Hydropower Engineering, chapter 3 · asked 2×
- RoR best installed capacity (NRs, 45 years) · Hydropower Engineering, chapter 3
- RoR at 40% exceedence; storage regulation · Hydropower Engineering, chapter 3
- RoR best installed capacity (USD 2795 million) · Hydropower Engineering, chapter 3
- Primary and secondary energy with 10% environmental flow · Hydro Power, chapter 3
- Primary and secondary energy (102 m head) · Hydro Power, chapter 3
- Micro hydro net head, power and energy · Energy Resources, chapter 5
- Wet and dry river intake · Water Supply Engineering, chapter 5