Power line carrier communication
Short answer
PLCC superimposes a 30–500 kHz HF carrier on the power line using coupling capacitors (block 50 Hz but pass HF) and wave traps (confine carrier to the line). The PLC terminal modulates/demodulates speech, data, and protection signals; line matching unit matches impedances. This provides telephony, SCADA data, and teleprotection without separate communication lines.
Describe how communication between two electric sub-stations can be made with Power Line Carrier Communication system.
Power Line Carrier Communication (PLCC) uses the high-voltage transmission line itself as the medium to send speech, data, telemetry and protection signals between two substations, by superimposing a high-frequency carrier (about 30–500 kHz) on the 50 Hz power.
Substation A Substation B
bus bus
| |
[WT]=========== HV line ================[WT]
| |
[CC] [CC]
| |
[LMU] [LMU]
| |
PLC terminal PLC terminal
(tx/rx: speech, data, teleprotection)
Components and working
- PLC terminal (transmitter/receiver): modulates the speech/data/protection signal on to an HF carrier at the sending end and demodulates it at the receiving end.
- Coupling capacitor (CC): high-voltage capacitor that passes the HF carrier to the line but blocks the 50 Hz power frequency.
- Line matching unit (LMU): matches the impedance of the coaxial cable to the line and, with the CC, forms a high-pass filter; it also provides surge protection and earthing switch.
- Wave trap (line trap): a parallel LC circuit in series with the line, tuned to the carrier frequency. It offers high impedance to the carrier, so the signal does not leak into the substation bus, but negligible impedance to 50 Hz power.
The carrier travels along the line conductors (phase-to-earth or phase-to-phase coupling) to the other substation, where it is picked up through its own CC and LMU.
Uses
- Telephone (speech) between substations and load dispatch centre.
- Teleprotection: carrier-aided distance and inter-tripping.
- SCADA data and telemetering.
Merits
- No separate communication line needed; the line is strong and reliable.
- Economical over long distances.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fire fighting system in power station · Power Plant Equipment, chapter 4 · asked 5×
- SCADA in a power system · Power Plant Equipment, chapter 4 · asked 4×
- Function of reactor in power system · Power Plant Equipment, chapter 4 · asked 3×
- Reactors in stations: merits and demerits · Power Plant Equipment, chapter 4
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Reactor schemes in stations and substations · Power Plant Equipment, chapter 4
- T1 digital carrier system; adaptive delta modulation · Communication Systems, chapter 5
- Numerical: λ/4 monopole and two-ray received power · Wireless Communication, chapter 3
- Speed-time curves: urban, sub-urban, main line · Utilization of Electrical Energy, chapter 4
- Power/light sub-circuits and cable for 50 kW, 60 kW · Industrial Power Distribution and Illumination, chapter 5 · asked 4×