- 2072 Chaitra · 4 marks
EMF per turn Et = K√kVA
Short answer
With rating Q = E_t·AT ×10⁻³ and a constant ratio r = φ_m/AT, we get φ_m = √(r Q×10³/(4.44f)). Then E_t = 4.44f φ_m = √(4.44 f r×10³) √Q, so E_t = K √(kVA) where K depends on frequency and the magnetic‑to‑electric loading ratio.
For a transformer show that the emf per turn Et is given by Et = K√kVA where kVA = rating of transformer.
The emf per turn is fixed by the ratio of magnetic loading to electric loading, which designers keep nearly constant for a given type of transformer.
Proof (single-phase)
Rating in kVA:
where (ampere-turns per winding) and .
Let the ratio of magnetic to electric loading be
Then
Hence
For a given frequency and a fixed ratio (chosen for minimum cost), is constant.
Typical values of K
| Transformer | K |
|---|---|
| 1-ph shell type | 1.0–1.2 |
| 1-ph core type | 0.75–0.85 |
| 3-ph shell type | 1.3 |
| 3-ph core, distribution | 0.45 |
| 3-ph core, power | 0.6–0.7 |
✓ Answer checked by Claude Sonnet 5.5
Related questions
- New kVA rating with fan cooling (350 kVA) · Electric Machine Design, chapter 2 · asked 2×
- New kVA rating with fan cooling (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Heating constant and 1-hour rating (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Heating constant and 1-hour rating (40 kVA) · Electric Machine Design, chapter 2 · asked 2×
- New kVA rating with fan cooling (150 kVA) · Electric Machine Design, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- Back emf and new current of 5 kVA motor · Electric Machines II, chapter 2 · asked 3×
- Back emf and new current of 9 kVA motor · Electric Machines II, chapter 2 · asked 3×
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×