Symmetrical fault at bus 3

Short answer

Convert the line delta to star: X_th = 0.34 pu on 100 MVA base. Fault current = 1 / 0.34 = 2.94 pu, fault level = 294 MVA. Actual amperes depend on the bus voltage base.

A 3-phase symmetrical fault occurs at bus 3 in the given power system network. Determine the fault current. Per unit values of reactance are based on 100 MVA base. [Figure: generator j0.1 (Y grounded) through transformer j0.1 (Y grounded/Y grounded) to bus 1; generator j0.2 (Y grounded) through transformer j0.2 (Δ/Y grounded) to bus 2; line 1-2 j0.8; line 1-3 j0.4; line 2-3 j0.4]

A three-phase fault is balanced, so only the positive-sequence network is used; the transformer connections (Y/Δ) and grounding do not affect it. Pre-fault voltage is 1.0 pu and load current is neglected.

Positive-sequence network

  • Source 1 to bus 1: 0.1+0.1=0.20.1 + 0.1 = 0.2 pu.
  • Source 2 to bus 2: 0.2+0.2=0.40.2 + 0.2 = 0.4 pu.
  • Lines: X12=0.8X_{12} = 0.8, X13=0.4X_{13} = 0.4, X23=0.4X_{23} = 0.4 pu (a delta between buses 1, 2, 3).

Delta-star conversion of the line delta

X1=X12X13X12+X13+X23=0.8×0.41.6=0.20X2=X12X231.6=0.8×0.41.6=0.20X3=X13X231.6=0.4×0.41.6=0.10\begin{aligned} X_1 &= \frac{X_{12}X_{13}}{X_{12} + X_{13} + X_{23}} = \frac{0.8 \times 0.4}{1.6} = 0.20 \\ X_2 &= \frac{X_{12}X_{23}}{1.6} = \frac{0.8 \times 0.4}{1.6} = 0.20 \\ X_3 &= \frac{X_{13}X_{23}}{1.6} = \frac{0.4 \times 0.4}{1.6} = 0.10 \end{aligned}
 E=1-j0.2-bus1-j0.2-+
                    N--j0.1--bus3 (F)
 E=1-j0.4-bus2-j0.2-+

Thevenin reactance at bus 3

Xpath1=0.2+0.20=0.40,Xpath2=0.4+0.20=0.60Xth=0.40×0.600.40+0.60+0.10=0.24+0.10=0.34 pu\begin{aligned} X_{path1} &= 0.2 + 0.20 = 0.40, \quad X_{path2} = 0.4 + 0.20 = 0.60 \\ X_{th} &= \frac{0.40 \times 0.60}{0.40 + 0.60} + 0.10 = 0.24 + 0.10 = 0.34\ \text{pu} \end{aligned}

(The same value is Z33Z_{33} of the bus impedance matrix.)

Fault current

If=VfjXth=1j0.34=−j2.9412 puFault MVA=1000.34=294.1 MVA\begin{aligned} I_f &= \frac{V_f}{jX_{th}} = \frac{1}{j0.34} = -j2.9412\ \text{pu} \\ \text{Fault MVA} &= \frac{100}{0.34} = 294.1\ \text{MVA} \end{aligned}

Answer: If=2.941I_f = 2.941 pu (fault level 294.1 MVA on the 100 MVA base). The current in amperes is If×IbaseI_f \times I_{base} once the bus voltage base is known.