- 2072 Kartik · 4 marks
Symmetrical fault at bus 3
Short answer
Convert the line delta to star: X_th = 0.34 pu on 100 MVA base. Fault current = 1 / 0.34 = 2.94 pu, fault level = 294 MVA. Actual amperes depend on the bus voltage base.
A 3-phase symmetrical fault occurs at bus 3 in the given power system network. Determine the fault current. Per unit values of reactance are based on 100 MVA base. [Figure: generator j0.1 (Y grounded) through transformer j0.1 (Y grounded/Y grounded) to bus 1; generator j0.2 (Y grounded) through transformer j0.2 (Δ/Y grounded) to bus 2; line 1-2 j0.8; line 1-3 j0.4; line 2-3 j0.4]
A three-phase fault is balanced, so only the positive-sequence network is used; the transformer connections (Y/Δ) and grounding do not affect it. Pre-fault voltage is 1.0 pu and load current is neglected.
Positive-sequence network
- Source 1 to bus 1: pu.
- Source 2 to bus 2: pu.
- Lines: , , pu (a delta between buses 1, 2, 3).
Delta-star conversion of the line delta
E=1-j0.2-bus1-j0.2-+
N--j0.1--bus3 (F)
E=1-j0.4-bus2-j0.2-+
Thevenin reactance at bus 3
(The same value is of the bus impedance matrix.)
Fault current
Answer: pu (fault level 294.1 MVA on the 100 MVA base). The current in amperes is once the bus voltage base is known.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×