Power angle depends on real power

Short answer

From the complex power expression, P = (Ef Vt / Xs) sin δ and Q = (Ef Vt cos δ – Vt^2)/Xs. The angle δ arises from the quadrature component of Ef, which is proportional to P/Xs; at zero real power, δ = 0 regardless of reactive load, showing δ is due solely to real power.

Using appropriate mathematical derivations, [show that] the phase angle (power/loading angle) δ between Ef and Vt is due solely to the real power delivered by the synchronous generator.

Consider a cylindrical-rotor synchronous generator with internal emf Ef∠δE_f\angle\delta, terminal voltage Vt∠0∘V_t\angle 0^\circ, synchronous reactance XsX_s and negligible armature resistance.

Derivation

Armature current:

Ia=Ef∠δ−Vt∠0jXsI_a = \frac{E_f\angle\delta - V_t\angle 0}{jX_s}

Complex power delivered at the terminal:

S=VtIa∗=Vt[Ef∠−δ−Vt−jXs]=jVt(Efcos⁡δ−jEfsin⁡δ−Vt)Xs=VtEfsin⁡δXs+j VtEfcos⁡δ−Vt2Xs\begin{aligned} S &= V_tI_a^* = V_t\left[\frac{E_f\angle -\delta - V_t}{-jX_s}\right] = \frac{jV_t\left(E_f\cos\delta - jE_f\sin\delta - V_t\right)}{X_s} \\ &= \frac{V_tE_f\sin\delta}{X_s} + j\,\frac{V_tE_f\cos\delta - V_t^2}{X_s} \end{aligned}

So

P=EfVtXssin⁡δ,Q=Vt(Efcos⁡δ−Vt)XsP = \frac{E_fV_t}{X_s}\sin\delta,\qquad Q = \frac{V_t(E_f\cos\delta - V_t)}{X_s}

Showing δ is due to real power alone

Write Ia=Iacos⁡ϕ−jIasin⁡ϕI_a = I_a\cos\phi - jI_a\sin\phi (lagging). Then

Ef=Vt+jXsIa=(Vt+XsIasin⁡ϕ)+j XsIacos⁡ϕE_f = V_t + jX_sI_a = (V_t + X_sI_a\sin\phi) + j\,X_sI_a\cos\phi tan⁡δ=XsIacos⁡ϕVt+XsIasin⁡ϕ\tan\delta = \frac{X_sI_a\cos\phi}{V_t + X_sI_a\sin\phi}
  • The imaginary (quadrature) part of EfE_f, which creates the angle δ\delta, is XsIacos⁡ϕ=XsP/VtX_sI_a\cos\phi = X_sP/V_t, i.e. proportional only to real power.
  • The reactive current Iasin⁡ϕI_a\sin\phi adds only to the in-phase part of EfE_f, changing its magnitude, not producing any angle by itself.

Two limiting cases make this clear:

  1. P = 0 (pure reactive load, cos⁡ϕ=0\cos\phi = 0): Efsin⁡δ=0E_f\sin\delta = 0, so δ=0\delta = 0 however large Q is; EfE_f and VtV_t are in phase and differ only in magnitude.
  2. Q = 0 (unity pf): Ef=Vt+jXsIaE_f = V_t + jX_sI_a, and δ=tan⁡−1(XsIa/Vt)\delta = \tan^{-1}(X_sI_a/V_t), a non-zero angle set by P.

Hence the power angle δ\delta between EfE_f and VtV_t exists only because real power is delivered (δ=0⇔P=0\delta = 0 \Leftrightarrow P = 0), while Q affects mainly the magnitude of EfE_f. This is the basis of P–δ (P–f) and Q–V decoupling.