Maximum steady state power with Vt held

Short answer

When the generator terminal voltage is held at 1.1 pu, the maximum steady-state power transfer is limited by the series reactance to (1.1×1.0)/1.0 = 1.1 pu, occurring at 90° angle between terminal and infinite bus voltages.

Find the maximum steady state power capability of a system consisting of a generator equivalent reactance of 0.4 pu connected to an infinite bus through a series reactance of 1.0 pu. The terminal voltage of the generator is held at 1.1 pu and the voltage of the infinite bus is 1.0 pu.

When the terminal voltage ∣Vt∣|V_t| is held constant (by a fast voltage regulator), the generator terminal bus transfers power to the infinite bus through the series reactance XeX_e:

P=∣Vt∣ ∣V∣Xesin⁡θP = \frac{|V_t|\,|V|}{X_e}\sin\theta

where θ\theta is the angle between VtV_t and VV. The power is largest when θ=90∘\theta = 90^\circ. The angle between EE and VV is then more than 90∘90^\circ, which is acceptable because the regulator raises EE as the load angle grows.

Data: Xg=0.4X_g = 0.4 pu, Xe=1.0X_e = 1.0 pu (series reactance), ∣Vt∣=1.1|V_t| = 1.1 pu, V=1.0∠0∘V = 1.0\angle0^\circ pu.

Step 1: Maximum power

Pmax=∣Vt∣ ∣V∣Xe=1.1×1.01.0=1.1 puP_{max} = \frac{|V_t|\,|V|}{X_e} = \frac{1.1\times 1.0}{1.0} = 1.1\ \text{pu}

Step 2: Check that this point is feasible

At the limit, Vt=j1.1V_t = j1.1 pu. The current is

I=Vt−VjXe=j1.1−1j1.0=1.1+j1.0 puI = \frac{V_t - V}{jX_e} = \frac{j1.1 - 1}{j1.0} = 1.1 + j1.0\ \text{pu}

so P=Re(VI∗)=1.1P = \text{Re}(V I^*) = 1.1 pu. The required internal emf is

E=Vt+jXgI=j1.1+j0.4(1.1+j1.0)=−0.4+j1.54=1.591∠104.6∘ puE = V_t + jX_gI = j1.1 + j0.4(1.1 + j1.0) = -0.4 + j1.54 = 1.591\angle104.6^\circ\ \text{pu}

Check: EVXg+Xesin⁡δ=1.591×11.4sin⁡104.6∘=1.10\dfrac{EV}{X_g + X_e}\sin\delta = \dfrac{1.591\times 1}{1.4}\sin104.6^\circ = 1.10 pu.

Comparison with constant EE

If EE were fixed and the limit were taken at δ=90∘\delta = 90^\circ, then Vt=1.1V_t = 1.1 pu would need E=1.487E = 1.487 pu, giving only Pmax=EV/X=1.487/1.4=1.062P_{max} = EV/X = 1.487/1.4 = 1.062 pu. If EE were simply taken as 1.1 pu, the limit would be 1.1/1.4=0.7861.1/1.4 = 0.786 pu. Holding VtV_t constant with the regulator raises the limit to ∣Vt∣∣V∣/Xe|V_t||V|/X_e.

Answer: Maximum steady-state power capability Pmax=1.1P_{max} = 1.1 pu (at θ=90∘\theta = 90^\circ between VtV_t and VV, with E=1.59E = 1.59 pu).

✓ Answer checked by Claude Sonnet 5.5

All Power System Analysis II chapter 6 questions →