Ybus with generator and transformer impedances

Short answer

Treat generator plus transformer reactances as shunt admittances to ground. Compute line admittances from impedances. Diagonal Y_ii sum of connected admittances; off-diagonal Y_ik = –y_ik. Ybus = [[11.0061–j33.2003, –4.1096+j10.9589, –6.8966+j17.2414]; [–4.1096+j10.9589, 10.0267–j29.3268, –5.9172+j14.2012]; [–6.8966+j17.2414, –5.9172+j14.2012, 12.8137–j31.4426]] pu.

Form the Ybus matrix for the following network. All impedance values are in per unit system. [Figure: G1 through T1 to bus 1; G2 through T2 to bus 2; line L1 between buses 1 and 2, L2 between buses 1 and 3, L3 between buses 2 and 3]

ComponentG1G2T1T2L1L2L3
Z, puj0.1j0.12j0.1j0.120.03+j0.080.02+j0.050.025+j0.06

Each generator reactance is in series with its transformer, so it forms a shunt branch from its bus to the reference (the generator emf is a current injection). Bus 3 has no generator.

Admittances

BranchImpedance (pu)Admittance (pu)
G1 + T1 at bus 1j0.1+j0.1=j0.2j0.1 + j0.1 = j0.2−j5-j5
G2 + T2 at bus 2j0.12+j0.12=j0.24j0.12 + j0.12 = j0.24−j4.1667-j4.1667
L1 (1-2)0.03+j0.080.03 + j0.084.1096−j10.95894.1096 - j10.9589
L2 (1-3)0.02+j0.050.02 + j0.056.8966−j17.24146.8966 - j17.2414
L3 (2-3)0.025+j0.060.025 + j0.065.9172−j14.20125.9172 - j14.2012

Example: y12=0.03−j0.080.032+0.082=0.03−j0.080.0073=4.1096−j10.9589y_{12} = \dfrac{0.03 - j0.08}{0.03^2 + 0.08^2} = \dfrac{0.03 - j0.08}{0.0073} = 4.1096 - j10.9589.

Elements

Y11=−j5+y12+y13=11.0061−j33.2003Y22=−j4.1667+y12+y23=10.0267−j29.3268Y33=y13+y23=12.8137−j31.4426\begin{aligned} Y_{11} &= -j5 + y_{12} + y_{13} = 11.0061 - j33.2003 \\ Y_{22} &= -j4.1667 + y_{12} + y_{23} = 10.0267 - j29.3268 \\ Y_{33} &= y_{13} + y_{23} = 12.8137 - j31.4426 \end{aligned}

Answer:

Ybus=[11.0061−j33.2003−4.1096+j10.9589−6.8966+j17.2414−4.1096+j10.958910.0267−j29.3268−5.9172+j14.2012−6.8966+j17.2414−5.9172+j14.201212.8137−j31.4426] puY_{bus} = \begin{bmatrix} 11.0061 - j33.2003 & -4.1096 + j10.9589 & -6.8966 + j17.2414 \\ -4.1096 + j10.9589 & 10.0267 - j29.3268 & -5.9172 + j14.2012 \\ -6.8966 + j17.2414 & -5.9172 + j14.2012 & 12.8137 - j31.4426 \end{bmatrix}\ \text{pu}

✓ Answer checked by Claude Sonnet 5.5