- 2076 Asoj · 10 marks
Footing for 1600 kN with shear check
Short answer
Service load = 1600/1.5 = 1066.7 kN; area = 1.1*1066.7/180 = 6.52 m², provide 2.6 m square. Factored pressure 236.7 kN/m²; depth D=550 mm (d=490 mm). Reinforcement 12 mm @ 130 c/c both ways; shear safe. Bearing stress 10 MPa > 9 MPa, excess 160 kN carried by column dowels.
Design an isolated footing to carry an axial factored load of 1600 kN. The column is 400 mm by 400 mm in size with 20 mm dia longitudinal bars. The bearing capacity of soil is 180 kN/m. For footing, adopt M20 concrete and 415 grade HSD bars. Check for shear is necessary.
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Given loads are factored: kN. Service loads = factored / 1.5: kN.
- Allowable (safe) bearing capacity of soil = 180 kN/m².
- The load of 1600 kN is a factored load.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 6.76 m² 6.52 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 372.3 | 2183 | 12 mm @ 130 c/c | 2262 |
| Along (width ) | 372.3 | 2183 | 12 mm @ 130 c/c | 2262 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1050 mm along , 1050 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 160 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels, which is adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 550 - 50 - 24 = 476 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 550 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.6 m, B = 2.6 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 2.6 m × 2.6 m × 550 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Isolated footing 500x500, 1600 kN · Design of RCC Structure, chapter 11
- Footing with load transfer check, 1000 kN · Design of RCC Structure, chapter 11
- Isolated footing 350x350, 1500 kN · Design of RCC Structure, chapter 11
- Footing 350x350, 8-16 mm bars, reversible moment · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Circular footing 1 m dia, 1000 kN · Foundation Engineering, chapter 6
- Braced built-up column, 3 m, 1600 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×
- Check 25 cm x 25 cm Sal column, 200 kN + 20 kNm · Design of Steel and Timber Structure, chapter 11