- 2081 Shrawan · 2+3+3+4+4 marks
Design: 220 m head plant, optimal voltage
Short answer
Design discharge Q45% minus riparian release is 6.557 m³/s, net head 209 m. Generator output 11.737 MW. Two 5.9 MW units, 7 MVA, 11 kV. Optimal transmission voltage 66 kV, single circuit. Turbine: 4-jet Pelton at 375 rpm. Unit scheme.
A typical hydro power plant has the following details.
| Month | Discharge (m³/s) | Flow duration | Discharge (m³/s) |
|---|---|---|---|
| Jan | 4.68533 | Qmax (Q0) | 207.0024 m³/s |
| Feb | 3.867942 | Q25% | 18.2424 m³/s |
| Mar | 3.584017 | Q45% | 6.87999 m³/s |
| Apr | 4.553517 | Q65% | 4.706992 m³/s |
| May | 3.22678 | Q85% | 3.106132 m³/s |
| Jun | 12.77418 | Q95% | 2.17348 m³/s |
| July | 32.95867 | Qmin | 0.648732 m³/s |
| Aug | 40.26243 | ||
| Sept | 31.23782 | ||
| Oct | 15.05586 | ||
| Nov | 7.380238 | ||
| Dec | 4.858522 |
| Parameter | Value |
|---|---|
| Gross head | 220 m |
| Turbine efficiency | 90% |
| Generator efficiency | 97% |
| Transformer efficiency | 98% |
| Head loss | 5.00% |
| Riparian release | 10% |
| Generator sub-transient reactance | 21% |
| Transformer reactance | 9% |
| Transmission line inductance | 0.95 mH/km |
| Transmission line length | 25 km |
| Generator voltage level | 11 kV |
| Transmission voltage level and no. of circuits | Use optimal one |
Design a hydro power plant so as to obtain the following parameters. a) Installed capacity taking design discharge as Q45%. [2] b) Select the number of unit and turbine type. [3] c) Select the type of turbine. [3] d) Draw the single line diagram showing number of units, generator, power transformer and station transformer. [4] e) Calculate the rating of generator circuit breaker to be used in your design. [4]
Assumptions: riparian release = 10% of the driest monthly mean flow; net head = gross head minus 5% loss; kN/m³; generator power factor 0.85; base = 100 MVA. For fault levels the grid is taken as a source of 1,000 MVA at the 66 kV grid substation at the far end of the line (an assumed typical value, since grid data is not given).
Optimal transmission voltage and number of circuits
Use Still's formula for the economical voltage (L in km, P in kW):
The nearest standard voltage is 66 kV. Line current at 66 kV: A, which a single ACSR Dog or Wolf circuit carries easily. Choose 66 kV, single circuit: an 11.8 MW plant does not justify the extra cost of a second circuit, and 33 kV would give high losses and voltage drop over 25 km.
a) Installed capacity at
Driest month = May (3.22678 m³/s), so riparian release m³/s.
Answer: generator output = 11.737 MW; power delivered to the 66 kV bus = 11.502 MW.
b) Number of units (turbine type in part c)
- Choose 2 units. With a run-of-river flow that falls well below the design flow in the dry months, one unit can run near full load on half the design flow, so efficiency stays high in winter.
- One unit can be maintained while the other runs, and two units keep the number of machines (and cost) low for a plant of this size.
- Per unit: m³/s, generator output MW → rate each unit at 5.9 MW.
- Generator rating: MVA → 7 MVA, 11 kV, 0.85 pf, 50 Hz.
- Step-up transformer, one per unit: 8 MVA, 11/66 kV, YNd11 (next standard size above 7 MVA).
Answer: installed capacity = 2 × 5.9 MW = 11.8 MW.
c) Type of turbine
m lies in the Francis (10–350 m) and Pelton (50–1300 m) ranges, so the specific speed decides.
Shaft power per unit kW. With (synchronous speeds) and , where :
| (rpm) | Poles | (metric, kW) |
|---|---|---|
| 1000 | 6 | 97.9 |
| 750 | 8 | 73.4 |
| 600 | 10 | 58.7 |
| 500 | 12 | 48.9 |
| 428.6 | 14 | 42.0 |
| 375 | 16 | 36.7 |
| 333.3 | 18 | 32.6 |
Usual ranges: Pelton about 10–30 per jet (multi-jet ), Francis about 60–300, Kaplan 300–1000.
Choose rpm (16 poles): . With 4 jets, , inside the Pelton range.
Check of jet ratio: jet velocity m/s; bucket speed ; runner diameter m; jet diameter m; , acceptable.
A Francis at 1000 rpm () is also possible, but the Pelton is preferred because (i) its efficiency stays nearly flat from about 20% to 100% load (jets can be switched off), which suits a run-of-river plant whose flow falls far below the design flow in the dry season, and (ii) it tolerates the heavy sediment of Himalayan rivers better, and worn buckets and needles are easier to repair.
Answer: 2 × vertical-axis 4-jet Pelton turbines, 375 rpm, about 6.05 MW each.
d) Single line diagram
Line to grid (66 kV, 25 km)
|
[CB]
|
===+=====+=============+=== 66 kV bus
| |
[CB] [CB]
| |
(T1) (T2)
| |
[CB] [CB]
| |
=========+====[BS]=====+=========+=== 11 kV bus
| | |
[GCB] [GCB] [CB]
| | |
(G1) (G2) (ST)
|
=================================+===+ 0.4 kV
|
[ACB]
|
(DG) black start
| Item | Rating |
|---|---|
| Generators G1–G2 | 7 MVA, 11 kV, 0.85 pf, 375 rpm, = 21% |
| Step-up transformers T1–T2 | 8 MVA each, 11/66 kV, YNd11, = 9% |
| Station transformer ST | 200 kVA, 11/0.4 kV, Dyn11, 4.5% (aux load about 1.5% of capacity) |
| Diesel generator DG | 125 kVA, 0.4 kV (essential auxiliaries for black start) |
| Line | 66 kV, single circuit, 25 km to grid substation |
| NGR | neutral grounding resistor (low-resistance earthing, one generator earthed at a time if preferred) |
BS = bus section breaker, GCB = generator circuit breaker, ACB = air circuit breaker. Black start: with the grid dead, the DG energises the 0.4 kV auxiliary bus (governor oil pumps, cooling water, excitation field flashing, lighting and battery chargers), one unit is started and runs in island mode, and it then energises the step-up transformer and the line.
e) Rating of generator circuit breaker
Per-unit reactances on 100 MVA base:
All generators feed the common 11 kV bus, so the GCB is rated for the full 11 kV bus fault level (generators plus the grid through the step-up transformers):
| Parameter | Required | Selected |
|---|---|---|
| Rated voltage | 11 kV system | 12 kV |
| Rated normal current | ≥ 459 A | 630 A |
| Breaking capacity | 186.6 MVA (9.79 kA) | 25 kA (520 MVA at 12 kV) |
| Making capacity | 24.97 kA peak | 63 kA peak |
| Short-time current | – | 25 kA, 3 s |
| Type | – | Vacuum (or SF6), generator-duty tested (IEEE C37.013) |
Answer: GCB fault level = 186.6 MVA; select a 12 kV, 630 A, 25 kA generator circuit breaker. The margin covers the DC component and delayed current zeros of generator faults; surge arresters and surge capacitors are fitted at the generator terminals when a VCB is used.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design: 250 m head plant at Q25% · Power Plant Design, chapter 4 · asked 14×
- Design: 120 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Design: 150 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Design: 120 m head plant, 33 kV · Power Plant Design, chapter 4 · asked 3×
- Design: 200 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 14×
- Design: 230 m head plant, 20 km line · Power Plant Design, chapter 4 · asked 14×
- Flow duration curve and power at mean flow · Hydropower Engineering, chapter 3
- Load duration curve; diesel plant; ROR flow duration · Hydropower Engineering, chapter 3
- Flow duration curve; firm and secondary energy · Hydropower Engineering, chapter 3
- Micro hydro net head, power and energy · Energy Resources, chapter 5