25 kVA transformer load voltage, half load
Short answer
Assume 0.8 pf lag. Secondary terminal voltage V2 ≈ 380 V (by exact voltage equation). Primary current I1 ≈ 1.14 A (neglecting no-load current).
A 25 KVA, single phase, 11 KV / 400 V transformer has impedance of primary and secondary 0.4 + j2 Ω and 0.02 + j1 Ω respectively. Determine the load terminal voltage and primary current at half load.
Given: 25 kVA, 11 kV/400 V. Primary impedance Z1 = 0.4 + j2 Ω; secondary Z2 = 0.02 + j1 Ω. Half load.
Assumptions (not stated in the question): the primary is supplied with the rated 11 kV; the load power factor is 0.8 lagging; the no-load current is neglected (not given).
Step 1: refer to the secondary
K = 400/11 000 = 0.03636, K² = 1.322×10⁻³.
R02 = R2 + K² R1 = 0.02 + 1.322×10⁻³ × 0.4 = 0.02053 Ω
X02 = X2 + K² X1 = 1.0 + 1.322×10⁻³ × 2 = 1.00264 Ω
Z02 = 0.02053 + j1.00264 Ω
Equivalent circuit (secondary side):
V1' = 400 V ──[0.0205 Ω]──[j1.0026 Ω]──┬── load V2
└── I2
Step 2: load current
Half-load: I2 = 0.5 × 25 000/400 = 31.25 A, at 0.8 lag (I2 = 31.25∠−36.87° A, with V2 as the reference).
Step 3: voltage drop and V2
I2 Z02 = 31.25∠−36.87° × (0.02053 + j1.00264)
= 19.31 + j24.68 V
V1' = V2 + I2 Z02 = 400 (magnitude)
(V2 + 19.31)² + 24.68² = 400²
V2 + 19.31 = √(160 000 − 609) = 399.24
V2 = 379.9 V
(The approximate formula, drop ≈ I2(R02 cos φ + X02 sin φ) = 31.25 × 0.618 = 19.3 V, gives V2 ≈ 380.7 V. The exact result is 379.9 V.)
Step 4: primary current
I1 = K × I2 = 0.03636 × 31.25 = 1.136 A
(For a unity pf load the terminal voltage would be about 398.1 V.)
Answer: load terminal voltage ≈ 380 V (secondary, at 0.8 pf lag); primary current ≈ 1.14 A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3