Instrument transformer vs power transformer

Short answer

Instrument transformers (CT and PT) step down high currents/voltages for measurement and protection with low VA burdens. Unlike power transformers, CTs operate near short circuit, PTs near open circuit; design emphasizes accuracy (low ratio and phase-angle errors) over efficiency, and core flux density is low.

What is meant by an instrument transformer? How they differ in principle of operation from that of power transformer? Explain with suitable diagram and mathematical expressions.

An instrument transformer is a special transformer used to step down high voltages or currents to safe, measurable values for meters and relays. It isolates the measuring circuit from the high-voltage line. There are two types: the current transformer (CT) and the potential transformer (PT).

Types and working

Current transformer. The primary has few turns (often a single bar) and is connected in series with the line. The secondary has many turns and feeds an ammeter or relay coil (low impedance burden). Its secondary is nearly short-circuited. Secondary current is 5 A or 1 A.

I1N1=I2N2⇒I1I2=N2N1=CT ratioI_1N_1 = I_2N_2 \Rightarrow \frac{I_1}{I_2} = \frac{N_2}{N_1} = \text{CT ratio}

Potential transformer. The primary is connected across the line, and the secondary feeds a voltmeter or pressure coil (high impedance burden). It works almost at no load, with secondary voltage 110 V.

V1V2=N1N2\frac{V_1}{V_2} = \frac{N_1}{N_2}
  Line ----+----- Load       Line ------+------
           |                            |
          [CT]--(A)                    [PT]--(V)

Difference from the power transformer

PointInstrument transformerPower transformer
PurposeMeasurement and protectionTransfer of power
RatingA few VA (burden)kVA to MVA
Primary current (CT)Decided by the line current (series)Decided by the secondary load
FluxCT: flux depends on line current; PT: constantConstant at all loads
Secondary conditionCT: nearly short-circuit; PT: nearly openVaries with the load
Main design aimHigh accuracy (small ratio and phase-angle error)High efficiency, good regulation
Core flux densityLow, to keep exciting current smallClose to saturation
Secondary openDangerous for CTSafe
ErrorsRatio and phase-angle errors matterNot a design concern

Errors

For a CT, the exciting current I0I_0 is drawn from the primary but does not appear in the secondary, so the actual ratio I1/I2I_1/I_2 differs from the turns ratio N2/N1N_2/N_1 (ratio error), and I2I_2 is not exactly 180° from I1I_1 (phase-angle error). Both errors are kept small by a low-loss, high-permeability core operated at low flux density and by a low burden.